Skip to content

Guides

1794-ADN discontinued: replacement spares and error 77

By TimControls Technical TeamPublished

Two Allen-Bradley 1794-ADN adapters: Series B with firmware 2.003 or earlier, and Series C with firmware 3.001 or later.

Product photos are for illustrative purposes only.

Share

Key takeaways

  • Rockwell discontinued the 1794-ADN on 22 October 2026 and names the 5094-AENTR as its engineering replacement.
  • A Series C spare reports a new major firmware revision and needs its own EDS file: if the scan list checks the major revision, expect error 73.
  • Out of box, firmware 2.003 and 3.001 or later allocate 32 point module words differently, so byte counts can match while the word allocation changes.
  • Record the firmware, the module list in slot order and the scanner's scan list before swapping, and test on an isolated bench.

Rockwell discontinued the Allen-Bradley 1794-ADN FLEX I/O DeviceNet adapter on 22 October 2026, according to its Rockwell lifecycle record. As documented in the 1794-ADN Installation Instructions (pages 7 and 8), the default I/O allocation changes when a newer spare is fitted to certain older racks with 32 point modules.

Before accepting a spare, verify which physical channels respond to the controller. Matching I/O byte counts alone cannot establish that the controller’s bits still map to the same points.

What to check before accepting a 1794-ADN replacement

CheckEvidence to record
Unit identityCatalogue number and series from the label, plus a diagnostic readout of the firmware revision.
Configuration on the spareFor a used unit, upload and record its configuration before dispatch where the tooling permits. If supplied reset, record how the default state was verified.
Scanner and engineering toolsThe scan list entry's electronic keying settings, expected input and output byte counts, and a working RSNetWorx setup with the EDS for the spare's firmware.
Auto-Device ReplacementWhether the scanner is set to restore a saved configuration to this node. If the scanner successfully restores a saved configuration, use the restored map for acceptance testing.
Station recovery filesThe saved adapter configuration where available, the scanner scan list, the modules in slot order and the controller I/O map.
Functional acceptanceOn an isolated bench, verify the connection, exercise the points the station uses and repeat the checks after a power cycle.

A supplier can document the unit’s identity and bench condition before dispatch. Acceptance for a specific station requires its configuration and point map, set up as described in Rockwell’s DeviceNet Network Configuration user manual.

As the installation instructions advise, disconnect all outputs from production equipment during testing and use simulated loads for output checks.

Why the same part number can produce error 77

In Rockwell’s list of DeviceNet status codes, error 77 means the data size expected by the device differs from the scanner’s scan list entry, and error 73 means the device identity does not match the scanner’s electronic key.

Check the keying first. According to the 1794-ADN Series C firmware release notes, the Series C adapter reports a new major firmware revision and needs its own EDS file. If the scan list entry checks the major revision, expect a Series B to Series C swap to fail the identity check, reported as error 73. If the configured key accepts the reported identity, check the I/O sizes next.

The 1794-ADN Installation Instructions (pages 7 and 8) describe replacing an adapter on firmware 2.003 or earlier with a Series C unit on firmware 3.001 or later. In the out of box configuration, meaning no rack configuration stored in the adapter, the two firmware generations allocate 16 bit words differently.

FLEX I/O moduleOlder default, firmware 2.003 or earlierNewer default, firmware 3.001 or later
1794-IB32 input module1 input word and 1 output word2 input words
1794-OB32P output module1 input word and 1 output word2 output words

The adapter instructions refer to the output module as the 1794-OB32; its catalogue number is 1794-OB32P, as the 1794-OB32P DC output module instructions show. Rockwell lists a firmware 2.004 input data anomaly corrected in 3.001 (installation instructions, page 7). Treat adapters on 2.004 as outside this comparison and verify them separately.

Rockwell says the older default made these modules behave as 16 point modules (installation instructions, page 8). The 1794-IB32 digital input module instructions (page 4) require a Series B adapter on firmware 2.4 or later for out of box compatibility. If the controller uses all 32 points of either module on firmware 2.003 or earlier, look for the downloaded configuration. Counting wired terminals alone cannot tell you which points the controller exchanges.

When the byte counts match

This example illustrates Rockwell’s published allocations. It has not been confirmed that this two slot rack can run in default mode on firmware 2.003 or earlier, since the IB32 instructions call for firmware 2.4 or later for out of box use. Put one 1794-IB32 in slot 0 and one 1794-OB32P in slot 1. Both adapters use their out of box configuration and the scan list is unchanged. The adapter’s input data starts with a status word, followed by each slot’s data in slot order. On the IB32, the first input word carries inputs 0 to 15, the second carries 16 to 31, and its output word sets the input filter time (1794-IB32 instructions, page 8). On the OB32P, the first output word drives outputs 0 to 15 and the second drives 16 to 31 (1794-OB32P instructions, page 8).

1794-ADN firmware 2.003 versus 3.001 I/O word map for 1794-IB32 and 1794-OB32P modules.
Illustration from Rockwell’s published allocations, not bench tested.
WordOlder default, firmware 2.003 or earlierNewer default, firmware 3.001 or later
Input 0Adapter statusAdapter status
Input 1IB32 inputs 0 to 15IB32 inputs 0 to 15
Input 2OB32P input word, not usedIB32 inputs 16 to 31
Output 0IB32 filter time settingOB32P outputs 0 to 15
Output 1OB32P outputs 0 to 15OB32P outputs 16 to 31

Both layouts total three input words and two output words. The calculated totals are identical. A byte count comparison alone would miss the change in word allocation.

Under the illustrated map, if the scanner connected and the controller kept its old map, the OB32P’s outputs 0 to 15 could be driven by the word the program previously sent as the IB32 filter time setting. The program’s intended output data could reach outputs 16 to 31, which an older default station does not use.

This allocation follows from the tables in the 1794-ADN Installation Instructions. Scanner acceptance and physical channel behaviour in this mixed rack example still require an isolated bench test.

Which recovery path applies?

These cases follow the 1794-ADN Installation Instructions (page 8). They assume the replacement is in its verified out of box state and that Auto-Device Replacement has not restored a different configuration to it. If it contains a saved configuration, identify and record it before applying the decision below.

  1. The original adapter used the older default. Confirm from the original map that the adapter used its default. If the controller uses all 32 points of an affected module, this case does not apply. For the documented size mismatch, update the scan list and adjust the controller I/O image and ladder references for any I/O that has shifted.
  2. The original adapter had a downloaded configuration that matches the newer default. Rockwell says the connection can establish. Once network setup is complete, it recommends writing the saved original configuration to the replacement adapter. Keep the project file separately as the recovery backup.
  3. The original adapter had a downloaded configuration that differs from the newer default. The replacement rejects configuration changing downloads while the scanner holds an active I/O connection. During the planned intervention, disable the adapter’s scan list entry in RSNetWorx or take the scanner off the DeviceNet network. Then download the saved original configuration, re-enable the entry and verify the point map.

Before the outage, use the maintenance laptop to confirm that RSNetWorx can identify and configure the actual spare. Rockwell provides FLEX I/O EDS files through the 1794-ADN product page. Registering an EDS and restoring the station configuration are separate steps, both covered in the DeviceNet Network Configuration user manual.

Series C adapters can be updated with ControlFLASH. The Series C firmware release notes provide no procedure for downgrading to firmware 2.x, so plan the scan list or configuration change rather than a firmware change.

Keeping FLEX I/O or moving to FLEX 5000?

Rockwell lists the 1794-AENTR as Active Mature. It is an option to evaluate if you want to retain compatible 1794 FLEX I/O and move the station to EtherNet/IP. Check each installed module and revision, controller support and the new I/O map.

The 5094-AENTR route, the replacement named in the 1794-ADN lifecycle record, moves the station to EtherNet/IP and FLEX 5000 hardware. Use Rockwell’s FLEX 5000 I/O migration guide to check the module selection, terminal bases and wiring.

Check the scanner’s lifecycle separately. Rockwell discontinued the SLC 1747-SDN DeviceNet scanner on 31 March 2024. If it is fitted, include it in the station’s recovery plan.

What to send for a quote

When requesting a 1794-ADN replacement quote from TimControls, include:

  • Catalogue number and series from the adapter label. A clear photo is useful.
  • Firmware revision reported by the installed adapter, if available.
  • FLEX I/O module catalogue numbers in slot order.
  • DeviceNet scanner catalogue number.
  • RSNetWorx project file: whether you have it for the station.

If the quote needs to include station specific bench acceptance, say so and have the scanner configuration and I/O map available for the test. Request a quote

Frequently asked questions

Is the 1794-ADN discontinued?
Yes. Rockwell lists the Allen-Bradley 1794-ADN as discontinued from 22 October 2026. If you're sourcing a spare, check the unit's firmware and configuration against the installed station.
What replaces the 1794-ADN?
Rockwell names the 5094-AENTR as its engineering replacement. It requires migration to EtherNet/IP and FLEX 5000 I/O. If retaining the 1794 FLEX I/O is a requirement, evaluate the 1794-AENTR against the installed modules and controller.

Related articles

View all

Can’t find your part? Send us the part number.