Read from the product label
- Maker
- Mitsubishi Electric
- Part no.
- FX5UJ-24MT/ES
- Serial / rev.
- as printed on your unit
Image is for illustrative purposes only. Please refer to product description.
Delivery options
Mitsubishi Electric FX5UJ-24MT/ES is a MELSEC iQ-F FX5UJ CPU module with 14 inputs and 10 transistor sink outputs built in and an AC power supply.
- Manufacturer
- Mitsubishi Electric
- Manufacturer part no.
- FX5UJ-24MT/ES
- Type
- MELSEC iQ-F FX5 CPU module
- Category
- PLCs & processors › CPU and processor modules
- Lifecycle
- Active
- OEM successor
- Not stated
- Technical datasheet
- Data sheet
Technical specifications
- Manufacturer
- Mitsubishi Electric
- Manufacturer part no.
- FX5UJ-24MT/ES
- Type
- MELSEC iQ-F FX5 CPU module
- Application
- PLC controller
- Used with
- MELSEC iQ-F expansion modules
- Control system
- Stored-program repetitive operation
- Input/output control system
- Refresh system; (Direct access input/output allowed by specification of direct access input/output [DX, DY])
- No. of input/output points, (1) No. of input/output points
- 256 points or less
- No. of input/output points, (2) No. of remote I/O points
- 256 points or less
- No. of input/output points, Total No. of points of (1) and (2)
- 256 points or less
- Programming specifications, Programming language
- Ladder diagram (LD), structured text (ST), function block diagram/ladder diagram (FBD/LD), sequential function chart (SFC)*; *For supported versions, refer to MELSEC iQ-F FX5 User's Manual (Application).
- Programming specifications, Programming extension function
- Function block (FB), function (FUN), label programming (local/global)
- Programming specifications, Constant scan
- 0.5 to 2000 ms (can be set in 0.1 ms increments)
- Programming specifications, Fixed cycle interrupt
- 1 to 60000 ms (can be set in 1 ms increments)
- Programming specifications, Timer performance specifications
- 100 ms, 10 ms, 1 ms
- Programming specifications, No. of program executions
- 32
- Programming specifications, No. of FB files
- 16 (Up to 15 for user)
- Command processing time, LD X0
- 34 ns
- Command processing time, MOV D0 D1
- 34 ns
- Memory capacity, Program capacity
- 48 k steps (96 kbytes, flash memory)
- Memory capacity, SD memory card
- Memory card capacity (SD/SDHC memory card: Max. 16 Gbytes)
- Memory capacity, Device/label memory
- 120 kbytes
- Memory capacity, Data memory/standard ROM
- 5 Mbytes
- Clock function, Display data
- Year, month, day, hour, minute, second, day of week (leap year automatic detection)
- Clock function, Precision
- Differences per month ±45 sec./25℃ (TYP)
- Power failure retention (clock data), Retention method
- Large-capacity capacitor; Clock data is retained using the power accumulated in a large-capacity capacitor incorporated into the PLC. When voltage of the large capacity capacitor drops, clock data is no longer accurately retained. The retention period of a fully charged capacitor (electricity is conducted across the PLC for at least 30 minutes) is 15 days (ambient temperature: 25℃). How long the capacitor can hold the data depends on the operating ambient temperature. When the operating ambient temperature is high, the holding period is short.
- Power failure retention (clock data), Retention time
- 15 days (ambient temperature: 25℃)
- Rated voltage
- 100 to 240 V AC
- Voltage fluctuation range
- -15%, +10%
- Frequency rating
- 50/60 Hz
Show all 103 specificationsShow fewer
- Allowable instantaneous power failure time
- Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.; When the supply voltage is 200 V AC or higher, the time can be change to 10 to 100 ms by editing the user program.
- Power fuse
- 250 V, 3.15 A Time-lag fuse
- Rush current
- 25 A max. 5 ms or less/100 V AC; 50 A max. 5 ms or less/200 V AC
- Power consumption
- 30 W; This item shows value when all 24 V DC service power supplies are used in the maximum configuration connectable to the CPU module. (The current of the input circuit is included.)
- 24 V DC service power supply capacity
- [When using 24 V DC service power supply for input circuit of CPU module]; 400 mA; [When using external power supply for input circuit of CPU module]; 460 mA; When I/O modules are connected, they consume current from the 24 V DC service power supply.; For details on the 24 V DC service power supply, refer to MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware).
- No. of input points
- 14 points
- Input connection type
- Removable terminal block (M3 screws)
- Input type
- Sink/source
- Input signal voltage
- 24 V DC +20%, -15%
- Input signal current, X0 to X7
- 5.3 mA/24 V DC
- Input signal current, X10 and subsequent
- 4.0 mA/24 V DC
- Input impedance, X0 to X7
- 4.3 kΩ
- Input impedance, X10 and subsequent
- 5.6 kΩ
- ON input sensitivity current, X0 to X7
- 3.5 mA or more
- ON input sensitivity current, X10 and subsequent
- 3.0 mA or more
- OFF input sensitivity current
- 1.5 mA or less
- Input response frequency, X0, X1, X3, X4
- 100 kHz; When capturing pulses of a response frequency of 50 to 100 kHz, refer to MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware).
- Input response frequency, X2, X5, X6, X7
- 10 kHz
- Pulse waveform, X0, X1, X3, X4
- T1 (pulse width): 5 μs or more; T2 (rise/fall time): 2.5 μs or less
- Pulse waveform, X2, X5, X6, X7
- T1 (pulse width): 50 μs or more; T2 (rise/fall time): 25 μs or less
- Input response time (H/W filter delay), X0, X1, X3, X4
- ON: 5 μs or less; OFF: 5 μs or less
- Input response time (H/W filter delay), X2, X5, X6, X7
- ON: 30 μs or less; OFF: 50 μs or less
- Input response time (H/W filter delay), X10 to X15
- ON: 50 μs or less; OFF: 150 μs or less
- Input response time (Digital filter setting value)
- None, 10 μs, 50 μs, 0.1 ms, 0.2 ms, 0.4 ms, 0.6 ms, 1 ms, 5 ms, 10 ms (initial values), 20 ms, 70 ms; When using this product in an environment with much noise, set the digital filter.
- Input signal format (Input sensor form)
- No-voltage contact input; Sink: NPN open collector transistor; Source: PNP open collector transistor
- Input circuit insulation
- Photo-coupler insulation
- Indication of input operation
- LED is lit when input is on
- No. of output points
- 10 points
- Output connection type
- Removable terminal block (M3 screws)
- Output type
- Transistor/sink output
- External power supply
- 5-30 V DC
- Max. load
- 0.5 A/point; The total load current per common terminal should be the following value.; 3 output points/common terminal: 0.6 A or less; 4 output points/common terminal: 0.8 A or less
- Open circuit leakage current
- 0.1 mA or less/30 V DC
- Voltage drop when ON, Y0 to Y2
- 1.0 V or less
- Voltage drop when ON, Y3 and subsequent
- 1.5 V or less
- Response time, Y0 to Y2
- 2.5 μs or less/10 mA or more (5-24 V DC)
- Response time, Y3 and subsequent
- 0.2 ms or less/200 mA or more (24 V DC)
- Output circuit insulation
- Photo-coupler insulation
- Indication of output operation
- LED is lit when output is on
- Clock function
- This function is used for the time management in the function which the system operates such as the date of the event history function, and data logging function.
- PID control function
- Performs PID control by the PID control instruction.
- Constant scan
- Keeps the scan time constant and executes program repeatedly.
- High-speed input/output function, High-speed counter function
- Performs high-speed counter, pulse width measurement, input interruption, etc. by using the input of the CPU module or high-speed pulse input/output module.
- High-speed input/output function, Pulse width measurement function
- Performs high-speed counter, pulse width measurement, input interruption, etc. by using the input of the CPU module or high-speed pulse input/output module.
- High-speed input/output function, Input interrupt function
- Performs high-speed counter, pulse width measurement, input interruption, etc. by using the input of the CPU module or high-speed pulse input/output module.
- High-speed input/output function, Positioning function
- Executes positioning operation by using the transistor output of the CPU module or high-speed pulse input/output module.
- High-speed input/output function, PWM output function
- Executes a PWM output by using the transistor output of the CPU module or high-speed pulse input/output module.
- Built-in Ethernet function
- An Ethernet related function such as connection to MELSOFT products and GOTs, socket communication, file transfer using FTP, Web server (HTTP), SNTP client, and simple CPU communication function.
- CC-Link IE Field Network Basic function
- This function exchanges data between the manager station and remote station using general-purpose Ethernet.
- Serial communication function
- A function related to the serial communication such as N:N Network, parallel link, MC protocol, inverter communication function and non-protocol communication.
- MODBUS communication function
- Connection with the products which support MODBUS RTU/TCP is available. The master and slave functions can be used.
- Operating ambient temperature
- 0 to 55℃, non-freezing; The simultaneous ON ratio of available PLC inputs or outputs changes with respect to the ambient temperature, refer to MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware).
- Storage ambient temperature
- -25 to 75℃, non-freezing
- Operating ambient humidity
- 5 to 95%RH, non-condensation; When used in a low-temperature environment, use in an environment with no sudden temperature changes. If there are sudden temperature changes because of opening/closing of the control panel or other reasons, condensation may occur, which may cause a fire, fault, or malfunction. Furthermore, use an air conditioner in dehumidifier mode to prevent condensation.
- Storage ambient humidity
- 5 to 95%RH, non-condensation
- Vibration resistance, Installed on DIN rail, Frequency: 5 to 8.4 Hz
- Half amplitude: 1.75 mm 10 times each in X, Y, Z directions (80 min in each direction); The criterion is shown in IEC61131-2.; When the system has equipment which specification values are lower than above mentioned vibration resistance specification values, the vibration resistance specification of the whole system is corresponding to the lower specification.
- Vibration resistance, Installed on DIN rail, Frequency: 8.4 to 150 Hz
- Acceleration: 4.9 m/s 2 10 times each in X, Y, Z directions (80 min in each direction); The criterion is shown in IEC61131-2.; When the system has equipment which specification values are lower than above mentioned vibration resistance specification values, the vibration resistance specification of the whole system is corresponding to the lower specification.
- Vibration resistance, Direct installing, Frequency: 5 to 8.4 Hz
- Half amplitude: 3.5 mm 10 times each in X, Y, Z directions (80 min in each direction); The criterion is shown in IEC61131-2.; When the system has equipment which specification values are lower than above mentioned vibration resistance specification values, the vibration resistance specification of the whole system is corresponding to the lower specification.
- Vibration resistance, Direct installing, Frequency: 8.4 to 150 Hz
- Acceleration: 9.8 m/s 2 10 times each in X, Y, Z directions (80 min in each direction); The criterion is shown in IEC61131-2.; When the system has equipment which specification values are lower than above mentioned vibration resistance specification values, the vibration resistance specification of the whole system is corresponding to the lower specification.
- Shock resistance
- 147 m/s 2 , Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z; The criterion is shown in IEC61131-2.
- Noise durability
- By noise simulator at noise voltage of 1000 Vp-p, noise width of 1 μs and period of 30 to 100 Hz
- Dielectric withstand voltage, Between power supply terminal (AC power supply) and ground terminal
- 1.5 kV AC for one minute
- Dielectric withstand voltage, Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal
- 500 V AC for one minute
- Dielectric withstand voltage, Between output terminal (transistor) and ground terminal
- 500 V AC for one minute
- Insulation resistance, Between power supply terminal (AC power supply) and ground terminal
- 10 MΩ or higher by 500 V DC insulation resistance tester
- Insulation resistance, Between 24 V DC service power supply connected to input terminal (24 V DC) and ground terminal
- 10 MΩ or higher by 500 V DC insulation resistance tester
- Insulation resistance, Between output terminal (transistor) and ground terminal
- 10 MΩ or higher by 500 V DC insulation resistance tester
- Grounding
- Class D grounding (grounding resistance: 100 Ω or less); (Common grounding with a heavy electrical system is not allowed); For grounding, refer to MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware).
- Working atmosphere
- Free from corrosive or flammable gas and excessive conductive dust
- Operating altitude
- 0 to 2000 m; The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
- Installation location
- Inside a control panel; The programmable controller is assumed to be installed in an environment equivalent to indoor.
- Overvoltage category
- II or less; This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
- Pollution degree
- 2 or less; This index indicates the degree to which conductive material is generated in the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. Temporary conductivity caused by condensation must be expected occasionally.
Technical documents (1)
Key features
- Built-in high-speed counter: Up to 4 ch 100 kHz + 4 ch 10 kHz
- Built-in positioning: Up to 200 kHz 3 axis
- Built-in Ethernet port: 1 ch
- Built-in USB port: 1 ch
- Program capacity 48 k steps (96 kbytes, flash memory)
About the Mitsubishi Electric FX5UJ-24MT/ES
The Mitsubishi Electric FX5UJ-24MT/ES is a MELSEC iQ-F FX5UJ CPU module, combining the CPU, I/O and power supply. Mitsubishi Electric's overview gives it 14 inputs (24 V DC sink/source) and 10 outputs (transistor sink). Built in, from the same overview: high-speed counter: Up to 4 ch 100 kHz + 4 ch 10 kHz; positioning: Up to 200 kHz 3 axis; Ethernet port: 1 ch. Mitsubishi Electric lists it as on sale.
What is the FX5UJ-24MT/ES used for?
The FX5UJ-24MT/ES controls a machine from its own 24 I/O; Mitsubishi Electric gives 256 points or less in total including remote I/O.
Lifecycle and successor
Active.
Before you order
What to photograph or confirm so the right unit is quoted.
Check the model name FX5UJ-24MT/ES on the rating plate, with the serial number and function version. Send us a photo of the rating plate and we will confirm the details before quoting.
Alternatives for FX5UJ-24MT/ES
The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.
| Product | Manufacturer | Type | Lifecycle | Relationship | Qty Available | Price | Action |
|---|---|---|---|---|---|---|---|
| Mitsubishi Electric FX5UJ-24MR/ESFX5UJ CPU Module, 24 I/O, Relay Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-24MT/ESSFX5UJ CPU Module, 24 I/O, Transistor Source Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-40MR/ESFX5UJ CPU Module, 40 I/O, Relay Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-40MT/ESFX5UJ CPU Module, 40 I/O, Transistor Sink Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-40MT/ESSFX5UJ CPU Module, 40 I/O, Transistor Source Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-60MR/ESFX5UJ CPU Module, 60 I/O, Relay Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-60MT/ESFX5UJ CPU Module, 60 I/O, Transistor Sink Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-60MT/ESSFX5UJ CPU Module, 60 I/O, Transistor Source Outputs, AC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-24MR/DSFX5UJ CPU Module, 24 I/O, Relay Outputs, DC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-24MT/DSFX5UJ CPU Module, 24 I/O, Transistor Sink Outputs, DC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-24MT/DSSFX5UJ CPU Module, 24 I/O, Transistor Source Outputs, DC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
| Mitsubishi Electric FX5UJ-40MR/DSFX5UJ CPU Module, 40 I/O, Relay Outputs, DC Supply | Mitsubishi Electric | MELSEC iQ-F FX5 CPU module | Active | Same family | On Request | On request | View › |
You may also be interested in
Mitsubishi Electric
Mitsubishi Electric Q100UDEHCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q00JCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q00JCPU-E
View ›Mitsubishi Electric
Mitsubishi Electric Q00CPU
View ›Mitsubishi Electric
Mitsubishi Electric Q01CPU
View ›Mitsubishi Electric
Mitsubishi Electric Q02CPU
View ›Mitsubishi Electric
Mitsubishi Electric Q02HCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q06HCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q12HCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q25HCPU
View ›Mitsubishi Electric
Mitsubishi Electric Q02CPU-A
View ›Mitsubishi Electric
Mitsubishi Electric Q02HCPU-A
View ›
TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.