Image is for illustrative purposes only. Please refer to product description.
Delivery options
Allen-Bradley 1756-OA16I ControlLogix AC output module: 16 individually isolated outputs, 74 to 265V AC, 2 A per point at 30 °C, one slot.
- Manufacturer
- Allen-Bradley
- Manufacturer part no.
- 1756-OA16I
- Product family
- ControlLogix I/O Modules (1756)
- Type
- Digital output module
- Category
- PLCs and I/O › Digital I/O modules
- Lifecycle
- Active
- OEM successor
- Not stated
- Technical datasheet
- Data sheet
Technical specifications
- Manufacturer
- Allen-Bradley
- Manufacturer part no.
- 1756-OA16I
- Type
- Digital output module
- Application
- I/O module
- Used with
- ControlLogix 1756 chassis
- Outputs
- 16 individually isolated
- Pilot duty
- Yes
- Voltage category
- 120/240V AC 50/60 Hz
- Operating voltage range
- 74…265V AC 47…63 Hz
- Output delay time
- 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz
- Current draw @ 5.1V
- 300 mA
- Current draw @ 24V
- 2.5 mA
- Total backplane power
- 1.59 W
- Power dissipation, max
- 5.5 W @ 60 °C (140 °F)
- Thermal dissipation
- 18.76 BTU/hr
- Off-state leakage current, max
- 3 mA per point
- On-state voltage drop, max
- 1.5V peak @ 2 A 6V peak @ load current < 50 mA
- Current per point, max
- 2 A @ 30 °C (86 °F) linear derating 1 A @ 60 °C (140 °F) linear derating
- Current per module, max
- 5 A @ 30 °C (86 °F) linear derating 4 A @ 60 °C (140 °F) linear derating
- Surge current per point
- 20 A for 43 ms per point, repeatable every 2 s @ 60 °C (140 °F)
- Load current, min
- 10 mA per point
- Commutating voltage
- 4V/µs for loads > 50 mA 0.2V/µs for loads < 50 mA
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the Coordinated System Time
- States in Fault mode per point
- Hold last state, On or Off (Off is default)
- Isolation voltage
- 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
- Inhibit voltage, max
- Zero crossing 60V peak
- Module keying
- Electronic, software configurable
- Fusing
- Not protected. A fused IFM is recommended to help protect outputs
- RTB keying
- User-defined mechanical
- Slot width
- 1
Show all 44 specificationsShow fewer
- Enclosure type
- None (open style)
- North American temperature code
- T4A
- Temperature, operating
- 0…60 °C (32…140 °F)
- Temperature, nonoperating
- -40…+85 °C (-40…+185 °F)
- Relative humidity
- 5…95% noncondensing
- Vibration
- 2 g @ 10…500 Hz
- Shock, operating
- 30 g
- Shock, nonoperating
- 50 g
- Emissions
- IEC 61000-6-4
- ESD immunity
- 6 kV contact discharges 8 kV air discharges
- Radiated RF immunity
- 10V/m with 1 kHz sine wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine wave 80% AM from 2000…2700 MHz
- EFT/B immunity
- ±4 kV at 5 kHz on signal ports
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
- Conducted RF immunity
- 10V rms with 1 kHz sine wave 80% AM from 150 kHz…80 MHz
Technical documents (1)
Key features
- 16 individually isolated outputs with pilot duty rating
- Operating voltage range of 74 to 265V AC at 47 to 63 Hz
- Fault mode per point: hold last state, On or Off, Off by default
- Electronic keying, software configurable, with user-defined mechanical RTB keying
- Scheduled outputs referenced to the Coordinated System Time
About the Allen-Bradley 1756-OA16I
The 1756-OA16I is a ControlLogix 74-265 VAC isolated output module with 16 points and a 36 pin connector. Each output is individually isolated, with an operating range of 74 to 265V AC at 47 to 63 Hz. Current is 2 A per point at 30 °C, derating linearly to 1 A at 60 °C, and 5 A per module at 30 °C, derating to 4 A at 60 °C. It is 1 slot wide.
What is the 1756-OA16I used for?
It switches AC loads in the 120/240V AC 50/60 Hz category where each output needs its own isolated circuit. Isolation is 250V continuous, basic insulation, between outputs and backplane and from output to output. The outputs are not protected, so a fused IFM is recommended to help protect them.
Lifecycle and successor
Active (Rockwell Automation lifecycle status, checked 24 October 2026).
Before you order
What to photograph or confirm so the right unit is quoted.
Read the catalog number 1756-OA16I, the series letter and the firmware revision from the label. Send us a photo of the label and we confirm the match before we quote.
Other parts in the Allen-Bradley ControlLogix I/O Modules family
Listed for reference. They differ from the 1756-OA16I in rating, supply, interface or function and are not interchangeable with it unless Allen-Bradley says so. Match the part number on your unit.
| Product | Type | Lifecycle | Qty Available | Price | Action |
|---|---|---|---|---|---|
| Allen-Bradley 1756-OW16IControlLogix 16 Point Isolated Relay Output Module | Digital output module | Active | On request | On request | View |
| Allen-Bradley 1756-IF16HControlLogix 16 Point HART Analog Input Module | Analog input module | Active | On request | On request | View |
| Allen-Bradley 1756-IF6IControlLogix 6 Point Isolated Analogue Input Module | Analog input module | Discontinued | On request | On request | View |
| Allen-Bradley 1756-IF8ControlLogix 8 Point A/I Module | Analog input module | Active | On request | On request | View |
| Allen-Bradley 1756-IF8IControlLogix 8 Point Isolated Analog Input Module | Analog input module | Active | On request | On request | View |
| Allen-Bradley 1756-IRT8IControlLogix 8 Point RTD/Thermocouple Input Module | Analog input module | Active | On request | On request | View |
| Allen-Bradley 1756-OA16ControlLogix 16 Point 74-265 VAC Output Module | Digital output module | Active | On request | On request | View |
| Allen-Bradley 1756-OB16DControlLogix 16 Point 24V DC Diagnostic Output Module | Digital output module | Active | On request | On request | View |
| Allen-Bradley 1756-OB16EControlLogix 16 Point Fused DC Output Module | Digital output module | Active | On request | On request | View |
| Allen-Bradley 1756-OB32ControlLogix 32 Point 12/24V DC Output Module | Digital output module | Active | On request | On request | View |
| Allen-Bradley 1756-OF8ControlLogix 8 Point Analog Output Module | Analog output module | Active | On request | On request | View |
| Allen-Bradley 1756-OF8IControlLogix 8 Point Isolated Analog Output Module | Analog output module | Active | On request | On request | View |
You may also be interested in

Allen-Bradley
Allen-Bradley 1734-OW4
ViewAllen-Bradley
Allen-Bradley 1756-L82E
ViewAllen-Bradley
Allen-Bradley 1769-IF16C
ViewAllen-Bradley
Allen-Bradley 1769-IF4XOF2
ViewAllen-Bradley
Allen-Bradley 1769-IQ16
ViewAllen-Bradley
Allen-Bradley 1769-IQ32
ViewAllen-Bradley
Allen-Bradley 1769-IR6
ViewAllen-Bradley
Allen-Bradley 1769-OB16
ViewAllen-Bradley
Allen-Bradley 1769-OF2
View
Allen-Bradley
Allen-Bradley 1769-OF4
ViewAllen-Bradley
Allen-Bradley 1769-OF4CI
ViewAllen-Bradley
Allen-Bradley 1769-OF8C
View
TimControls is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.