Skip to content
Industrial

NXL00095

Danfoss VACON NXL 0009 5, 9 A, 4 kW, 380-500 V, MF4

Danfoss

Delivery options

  • FedEx
  • DHL
  • UPS

Danfoss VACON NXL frequency converter type NXL00095: 4 kW motor at 380 V (5.5 kW at 500 V), low overload, mechanical size MF4, IP21 / IP54. Discontinued by Danfoss.

Manufacturer
Danfoss
Manufacturer part no.
NXL00095
Type
AC drive
Lifecycle
Discontinued
OEM successor
VACON 100 INDUSTRIAL or VACON 20
Technical datasheet
Data sheet

Technical specifications

Manufacturer
Danfoss
Manufacturer part no.
NXL00095
Type
AC drive
Application
AC motor speed control
Used with
Three-phase AC motors
Rated continuous current IL (low overload, 40 °C)
9 A
10 % overload current
9.9 A
Rated continuous current IH (high overload, 50 °C)
7.6 A
50 % overload current
11.4 A
Motor shaft power, low overload
4 kW at 380 V; 5.5 kW at 500 V (40 °C)
Motor shaft power, high overload
3 kW at 380 V; 4 kW at 500 V (50 °C)
Nominal input current
9 A
Mechanical size and enclosure
MF4, IP21 / IP54
Dimensions W x H x D
128x292x190 mm
Weight
5 kg
Mains voltage
380-500 V AC, -15 %...+10 %, 3~
Input frequency
45...66 Hz
Output voltage
0...Uin
Output frequency
0...320 Hz
Control method
Frequency control U/f; open-loop sensorless vector control
Switching frequency
1...16 kHz; factory default 6 kHz
Starting torque
150 % (low overload); 200 % (high overload)
Ambient operating temperature
-10 °C (no frost)...+50 °C at IH; -10 °C...+40 °C at IL
Storage temperature
-40 °C...+70 °C
Relative humidity
0...95 % RH, non-condensing

Technical documents (1)

Key features

  • Rated continuous current 9 A (low overload) / 7.6 A (high overload)
  • 4 kW motor at 380 V (5.5 kW at 500 V), low overload
  • Mechanical size MF4, IP21 / IP54
  • Output 0...320 Hz; U/f and open-loop sensorless vector control
  • Switching frequency 1...16 kHz
  • Danfoss lists the VACON NXL as discontinued (Inactive phase)

About the Danfoss NXL00095

The VACON NXL 0095 5 is a compact frequency converter from the VACON NXL range, now part of Danfoss. Danfoss's NXL user manual gives this type a rated continuous current of 9 A at low overload (40 °C) and 7.6 A at high overload (50 °C), 4 kW motor at 380 V (5.5 kW at 500 V), low overload, and mechanical size MF4 with IP21 / IP54 enclosure. The range runs U/f or open-loop sensorless vector control with an output of 0 to 320 Hz. Danfoss's product page states that the VACON NXL has reached the Inactive phase of its lifecycle, meaning it is discontinued and no longer in production, and names VACON 100 INDUSTRIAL and VACON 20 as successors.

What is the NXL00095 used for?

It controls the speed of a three-phase AC motor on pumps, fans, conveyors and small machines. A failed unit stops the motor it drives.

Lifecycle and successor

Discontinued.

OEM successor: VACON 100 INDUSTRIAL or VACON 20

Before you order

What to photograph or confirm so the right unit is quoted.

Read the full type code on the rating plate, for example NXL 0095 5 C2H1SSS / C5H1SSS. The digits after NXL give the rated current and the mains voltage (2 = 208-240 V, 5 = 380-500 V); the letters that follow give the keypad, enclosure (1 = IP20; 2 = IP21, 5 = IP54 on MF4 to MF6), EMC level and brake chopper. Send the whole code and any option boards fitted.

Alternatives for NXL00095

The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.

ProductManufacturerTypeLifecycleRelationshipQty AvailablePriceAction
VACON 100 INDUSTRIAL or VACON 20Named by the manufacturer as the successorDanfossAC driveNot checked; ask usOEM successor (upgrade path)On RequestOn requestView ›
Danfoss NXL00022VACON NXL 0002 2, 2.4 A, 0.37 kW, 208-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00032VACON NXL 0003 2, 3.7 A, 0.75 kW, 208-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00042VACON NXL 0004 2, 4.8 A, 1.1 kW, 208-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00062VACON NXL 0006 2, 6.6 A, 1.5 kW, 208-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00015VACON NXL 0001 5, 1.9 A, 0.55 kW, 380-500 V, MF2DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00025VACON NXL 0002 5, 2.4 A, 0.75 kW, 380-500 V, MF2DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00035 IP20VACON NXL 0003 5, 3.3 A, 1.1 kW, 380-500 V, MF3DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00045 IP20VACON NXL 0004 5, 4.3 A, 1.5 kW, 380-500 V, MF3DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00055 IP20VACON NXL 0005 5, 5.4 A, 2.2 kW, 380-500 V, MF3DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00035 IP21/IP54VACON NXL 0003 5, 3.3 A, 1.1 kW, 380-500 V, MF4DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00045 IP21/IP54VACON NXL 0004 5, 4.3 A, 1.5 kW, 380-500 V, MF4DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss NXL00055 IP21/IP54VACON NXL 0005 5, 5.6 A, 2.2 kW, 380-500 V, MF4DanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›

You may also be interested in

TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.

Need Danfoss NXL00095? Send us the details.