Skip to content
Industrial

Mitsubishi Electric L60RD8

MELSEC-L Analogue input module, 8 analogue input channels

Mitsubishi Electric
Mitsubishi Electric L60RD8, Mitsubishi Electric product photo

Image is for illustrative purposes only. Please refer to product description.

Delivery options

  • FedEx
  • DHL
  • UPS

Mitsubishi Electric L60RD8 is a MELSEC-L analogue input module with 8 analogue input channels.

Manufacturer part no.
L60RD8
Type
Analog input module
Lifecycle
Phased out
OEM successor
R60RD8-G
Technical datasheet
Data sheet

Technical specifications

Manufacturer
Mitsubishi Electric
Manufacturer part no.
L60RD8
Type
Analog input module
Application
I/O module
Used with
MELSEC-L CPU modules
Number of analog input points
8 points (8 channels)
Digital output, Temperature measured value
-3280...15620
Digital output, Scaling value
-32768...32767
Applicable resistance temperature detector
Pt100, JPt100, Pt1000, Pt50, Ni100, Ni120, Ni500, Cu100, Cu50
Measured temperature range, Pt100
Celsius: -20...120 ˚C, -200...850 ˚C; Fahrenheit: -4...248˚F, -328...1562˚F
Measured temperature range, JPt100
Celsius: -20...120 ˚C, -200...600 ˚C; Fahrenheit: -4...248˚F, -328...1112˚F
Measured temperature range, Pt1000
Celsius: -200...850 ˚C; Fahrenheit: -328...1562˚F
Measured temperature range, Pt50
Celsius: -200...650 ˚C; Fahrenheit: -328...1202˚F
Measured temperature range, Ni100
Celsius: -60...250 ˚C; Fahrenheit: -76...482˚F
Measured temperature range, Ni120
Celsius: -60...250 ˚C; Fahrenheit: -76...482˚F
Measured temperature range, Ni500
Celsius: -60...250 ˚C; Fahrenheit: -76...482˚F
Measured temperature range, Cu100
Celsius: -180...200 ˚C; Fahrenheit: -292...392˚F
Measured temperature range, Cu50
Celsius: -180...200 ˚C; Fahrenheit: -292...392˚F
Temperature detecting output current
1 mA: Pt100, JPt100, Pt50, Ni100, Ni120, Cu100, Cu50; 100 µA: Pt1000, Ni500
Resolution
0.1 ˚C
Accuracy
Accuracy (゚C) = (Conversion accuracy) + (Allowable difference of resistance temperature detector used)
Conversion accuracy, Pt100, -200...850 ゚C
Specified temperature × ±0.3 % or ±0.8 ˚C, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±2.7 ˚C, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt100, -20...120 ゚C
±0.6 ˚C (ambient temperature: 25±5 ゚C), ; ±2.0 ˚C (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt100, -4...248 ˚F
±1.1˚F (ambient temperature: 25±5 ゚C), ; ±3.6˚F (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt100, -328...1562 ˚F
Specified temperature × ±0.3 % or ±1.5˚F, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±4.9˚F, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, JPt100, -20...120 ゚C
±0.6 ˚C (ambient temperature: 25±5 ゚C), ; ±2.0 ˚C (ambient temperature: 0...55 ゚C)
Conversion accuracy, JPt100, -4...248 ˚F
±1.1˚F (ambient temperature: 25±5 ゚C), ; ±3.6˚F (ambient temperature: 0...55 ゚C)
Conversion accuracy, JPt100, -200...600 ゚C
Specified temperature × ±0.3 % or ±0.8 ˚C, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±2.7 ˚C, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, JPt100, -328...1112 ˚F
Specified temperature × ±0.3 % or ±1.5˚F, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±4.9˚F, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt1000, -200...850 ゚C
Specified temperature × ±0.3 % or ±0.8 ˚C, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±2.7 ˚C, whichever is greater (ambient temperature: 0...55 ゚C)
Show all 50 specifications
Conversion accuracy, Pt1000, -328...1562 ˚F
Specified temperature × ±0.3 % or ±1.5˚F, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±4.9˚F, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt50, -200...650 ゚C
Specified temperature × ±0.3 % or ±0.8 ˚C, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±4.1 ˚C, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Pt50, -328...1202 ˚F
Specified temperature × ±0.3 % or ±1.5˚F, whichever is greater (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±7.4˚F, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Ni100/Ni120/Ni500, -60...250 ゚C
±0.6 ˚C (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±1.4 ˚C, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Ni100/Ni120/Ni500, -76...482 ˚F
±1.1˚F (ambient temperature: 25±5 ゚C),; Specified temperature × ±0.8 % or ±2.6˚F, whichever is greater (ambient temperature: 0...55 ゚C)
Conversion accuracy, Cu100/Cu50, -180...200 ゚C
±0.8 ˚C (ambient temperature: 25±5 ゚C), ; ±2.7 ˚C (ambient temperature: 0...55 ゚C)
Conversion accuracy, Cu100/Cu50, -292...392 ˚F
±1.5˚F (ambient temperature: 25±5 ゚C), ; ±4.9˚F (ambient temperature: 0...55 ゚C)
Conversion speed
40 ms/channel
Disconnection detection
Available
Isolation method
Between input terminals and programmable controller power supply: Photocoupler; Between input channels: Non-isolation
Dielectric withstand voltage
Between input terminals and programmable controller power supply: 500 V AC rms for 1 minute; Between input channels: Non-isolation
Insulation resistance
Between input terminals and programmable controller power supply: 500 V DC, 10 MΩ or higher; Between input channels: Non-isolation
External interface
24-point spring clamp terminal block
Number of occupied I/O points
16 points (I/O assignment: Intelligent 16 points)
Internal current consumption (5 V DC)
0.22 A
External dimensions, Height
90 mm
External dimensions, Width
28.5 mm
External dimensions, Depth
116.5 mm
Weight
0.15 kg
General specifications
Refer to the general specifications of the CPU module or remote head module.

Technical documents (1)

Key features

  • Number of analog input points: 8 points (8 channels)
  • Digital output, Scaling value: -32768...32767
  • Resolution: 0.1 ˚C
  • Conversion speed: 40 ms/channel
  • Disconnection detection: Available

About the Mitsubishi Electric L60RD8

The Mitsubishi Electric L60RD8 is a MELSEC-L analogue input module. Mitsubishi Electric's overview: 8 channels, RTD (Pt100, JPt100, Pt1000, Pt50, Pt10, Ni100, Ni120, Ni500, Cu100, Cu50), conversion speed: 40 ms/channel, 24-point spring-clamp terminal block. Mitsubishi Electric names the R60RD8-G and FX5-8AD as replacement models.

What is the L60RD8 used for?

The L60RD8 joins a MELSEC-L system beside the CPU, with no base unit, and connects field signals to it.

Lifecycle and successor

Phased out.

OEM successor: R60RD8-G

Before you order

What to photograph or confirm so the right unit is quoted.

Check the model name L60RD8 on the rating plate, with the serial number and function version. Send us a photo of the rating plate and we will confirm the details before quoting.

Alternatives for L60RD8

The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.

ProductManufacturerTypeLifecycleRelationshipQty AvailablePriceAction
R60RD8-GNamed by the manufacturer as the successorMitsubishi ElectricAnalog input moduleActiveOEM successor (upgrade path)On RequestOn requestView ›
Mitsubishi Electric L60AD4MELSEC-L Analogue input module, 4 channelsMitsubishi ElectricAnalog input modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60AD4-2GHMELSEC-L Analogue input module, 4 channelsMitsubishi ElectricAnalog input moduleDiscontinuedSame familyOn RequestOn requestView ›
Mitsubishi Electric L60ADVL8MELSEC-L Analogue input module, 8 channelsMitsubishi ElectricAnalog input modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60ADIL8MELSEC-L Analogue input module, 8 channelsMitsubishi ElectricAnalog input modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60DA4MELSEC-L Analogue output module, 4 analogue output channelsMitsubishi ElectricAnalog output modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60DAVL8MELSEC-L Analogue output module, 8 analogue output channelsMitsubishi ElectricAnalog output modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60DAIL8MELSEC-L Analogue output module, 8 channels, input (resolution): 0...8000Mitsubishi ElectricAnalog output modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60AD2DA2MELSEC-L Analogue input module, Analog input: 2 channelsMitsubishi ElectricAnalog input modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60TCTT4MELSEC-L Temperature control module, 4 temperature input channelsMitsubishi ElectricTemperature control modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60TCTT4BWMELSEC-L Temperature control module, 4 temperature input channelsMitsubishi ElectricTemperature control modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60TCRT4MELSEC-L Temperature control module, 4 temperature input channelsMitsubishi ElectricTemperature control modulePhased outSame familyOn RequestOn requestView ›
Mitsubishi Electric L60TCRT4BWMELSEC-L Temperature control module, 4 temperature input channelsMitsubishi ElectricTemperature control modulePhased outSame familyOn RequestOn requestView ›

You may also be interested in

TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.

Need Mitsubishi Electric L60RD8? Send us the details.