Image is for illustrative purposes only. Please refer to product description.
- Manufacturer
- Allen-Bradley
- Manufacturer part number
- 1756-L72
- Product family
- ControlLogix and GuardLogix Controllers (1756)
- Category
- PLCs and I/O › CPU and processor modules
- Technical datasheet
- Data sheet
Specifications
| Attribute | Value |
|---|---|
| Type | ControlLogix controller |
| Manufacturer lifecycle | Active |
| Controller tasks | 32 tasks, including a combination of one continuous, periodic, and event tasks 32 programs/tasks prior to RSLogix 5000® programming software, version 15.01.00 100 programs/task beginning with RSLogix 5000 programming software, version 15.01.00 1000 programs/task beginning with Logix Designer application, version 24.00.00 |
| Built-in communication ports | 1-port USB |
| Communication options | EtherNet/IP, ControlNet, DeviceNet, Data Highway Plus, Remote I/O, SERCOS, Third-party process and device networks |
| USB port communication | Programming, configuration, firmware update, and online edits only |
| Controller connections supported max | 500 |
| Network connections, per network module | 1000 I/O; 528 EtherNet/IP; 512 TCP (1756-EN4TR) 256 EtherNet/IP; 128 TCP (1756-EN2x) 128 EtherNet/IP; 64 TCP (1756-ENBT) 100 ControlNet (1756-CN2/A) 40 ControlNet (1756-CNB/D, 1756-CNB/E) 128 ControlNet (1756-CN2/B) |
| Controller redundancy | Full support |
| Integrated motion | SERCOS interface, Analog options (encoder input, LDT input, SSI input), Integrated Motion on the EtherNet/IP network |
| Programming languages | Relay ladder logic, Structured text, Function Block Diagram, Sequential function chart (SFC) |
| User memory | 4 MB |
| I/O memory | 0.98 MB |
| Nonvolatile memory storage | 1 GB Secure Digital (SD) card (1784-SD1), ships pre-installed in the controller |
| Digital I/O max | 128,000 |
Show all 43 specificationsShow fewer specifications
| Analog I/O max | 4000 |
|---|---|
| Total I/O max | 128,000 |
| Energy storage module | 1756-ESMCAP, 1756-ESMCAPK capacitor energy storage module (removable, ships installed with every controller) 1756-ESMNSE, 1756-ESMNSEK capacitor energy storage module (removable, no residual WallClockTime power backup) 1756-ESMNRM, 1756-ESMNRMK capacitor energy storage module (non-removable, helps prevent USB connection and SD card use to help secure the controller) |
| Current draw @ 1.2V DC | 5 mA |
| Current draw @ 5.1V DC | 800 mA |
| Power dissipation | 2.5 W |
| Thermal dissipation | 8.5 BTU/hr |
| Isolation voltage | 30V (continuous), basic insulation type, USB port-to-system, Compliant and tested according to IEC/UL 61010-1 |
| USB port | USB 2.0, full speed (12 Mbps) |
| Weight approx | 0.25 kg (0.55 lb) |
| Slot width | 1 |
| Module location | Chassis-based, any slot |
| Chassis | 1756-A4, 1756-A4K, 1756-A7, 1756-A7K, 1756-A10, 1756-A10K, 1756-A13, 1756-A13K, 1756-A17, 1756-A17K |
| Power supply, standard | 1756-PA50, 1756-PA50K, 1756-PA72, 1756-PA72K, 1756-PA75, 1756-PA75K, 1756-PB50, 1756-PB50K 1756-PB72, 1756-PB72K, 1756-PB75, 1756-PB75K, 1756-PC75, 1756-PH75 |
| Power supply, redundant | 1756-PA75R, 1756-PA75RK, 1756-PB75R, 1756-PB75RK, 1756-PSCA2, 1756-PSCA2K |
| Wire category | 3 - on USB port |
| Temperature code | T4 |
| Enclosure type rating | None (open-style) |
| Temperature, operating | 0 °C ≤ Ta ≤ +60 °C (+32 °F ≤ Ta ≤ +140 °F) |
| Temperature, nonoperating | -40…+85 °C (-40…+185 °F) |
| Relative humidity | 5…95% noncondensing |
| Vibration | IEC 60068-2-6 (Test Fc, Operating) |
| Shock, operating | IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
| Shock, nonoperating | IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
| Emissions | IEC 61000-6-4 |
| ESD immunity | IEC 61000-4-2 |
| Radiated RF immunity | IEC 61000-4-3 |
| Conducted RF Immunity | IEC 61000-4-6 (Not applicable: USB is a temporary programming port.) |
Description
The Allen-Bradley 1756-L72 is a ControlLogix 4 MB controller, according to Rockwell Automation technical data 1756-TD001. Rockwell lists 4 MB of user memory, 0.98 MB of I/O memory and a maximum of 500 controller connections. It has a 1-port USB interface and is a single-slot, chassis-based module that can be fitted in any slot. Rockwell lists its lifecycle status as Active Mature.
Application: PLC controller
Used with: ControlLogix 1756 chassis
What is the 1756-L72 used for?
The controller runs the control program in a ControlLogix chassis. Rockwell lists EtherNet/IP, ControlNet, DeviceNet, Data Highway Plus, Remote I/O and SERCOS among its communication options, and integrated motion including SERCOS interface and Integrated Motion on the EtherNet/IP network. The USB port is for programming, configuration, firmware update and online edits only.
Key features
- 4 MB user memory and 0.98 MB I/O memory
- 1-port USB 2.0, full speed (12 Mbps)
- Full controller redundancy support
- Ladder, structured text, function block and SFC programming
- Chassis-based, 1 slot wide, fits any slot
Documents and Resources
Associated Products
| Image | Product | Description | Stock | View | Add to RFQ |
|---|---|---|---|---|---|
![]() | 1756-L71Allen-Bradley | ControlLogix 2 MB controller with SD card | In stock | View | |
![]() | 1756-L73Allen-Bradley | ControlLogix 8 MB controller, 1-port USB | In stock | View | |
![]() | 1756-L74Allen-Bradley | ControlLogix 16 MB controller, USB port | In stock | View | |
![]() | 1756-L75Allen-Bradley | ControlLogix 32 MB controller, USB port | In stock | View | |
![]() | 1756-L73XTAllen-Bradley | ControlLogix 8MB Controller L7XT | In stock | View | |
![]() | 1756-L61Allen-Bradley | ControlLogix 5560 controller, 2 MB memory | In stock | View | |
![]() | 1756-L63Allen-Bradley | ControlLogix 5560 controller, 8 MB memory | In stock | View | |
![]() | 1756-L62Allen-Bradley | ControlLogix 5560 controller, 4 MB memory | In stock | View | |
![]() | 1756-L64Allen-Bradley | ControlLogix 5560 controller, 16 MB memory | In stock | View | |
![]() | 1756-L65Allen-Bradley | ControlLogix 5560 controller, 32 MB memory | In stock | View | |
![]() | 1756-L81EAllen-Bradley | ControlLogix 5580 Controller with 3 MB Memory | In stock | View | |
![]() | 1756-L83EAllen-Bradley | ControlLogix 5580 Controller with 10 MB Memory | In stock | View |
Product Questions
Is the 1756-L72 discontinued?
No. Its manufacturer lifecycle status is Active.
Can another Allen-Bradley ControlLogix and GuardLogix Controllers part replace it?
Potential replacements must be checked against the required ratings, dimensions and connections. Sharing a family name does not establish interchangeability.
Do you ship worldwide?
Yes. TimControls ships worldwide. Parts usually ship within 3 to 7 working days of order confirmation, and the exact lead time and shipping options are stated on your quote. Include your delivery country and postal code when you ask for a quote.
Related Products
Allen-Bradley
1756-L8SPXTGuardLogix 5580 XT Partner Module
Same ControlLogix and GuardLogix Controllers system
In stock
Allen-Bradley
1756-L8XTSPGuardLogix 5580 XT Partner Module
Same ControlLogix and GuardLogix Controllers system
In stock
Latest news
TimControls is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.