VLT 5122 525-690 V

Danfoss VLT 5000 type 5122, 110 kW, 3 x 525-690 V

Danfoss

Delivery options

  • FedEx
  • DHL
  • UPS

Danfoss VLT 5122 frequency converter from the VLT 5000 series for 3 x 525-690 V: 110 kW, output current 162 A. Discontinued by Danfoss; successor iC7-Automation.

Manufacturer
Danfoss
Manufacturer part no.
VLT 5122 525-690 V
Type
AC drive
Lifecycle
Discontinued
OEM successor
iC7-Automation
Technical datasheet
Data sheet

Technical specifications

Manufacturer
Danfoss
Manufacturer part no.
VLT 5122 525-690 V
Type
AC drive
Application
AC motor speed control
Used with
Three-phase AC motors
Mains supply
3 x 525-690 V
Normal overload torque (110 %) / Output current I VLT,N [A] (525-550 V)
162
Normal overload torque (110 %) / Output current I VLT,N [A] (551-690 V)
155
Normal overload torque (110 %) / Output current I VLT,MAX (60 s) [A]
171
Normal overload torque (110 %) / Output S VLT,N [kVA] (550 V)
154
Normal overload torque (110 %) / Output S VLT,N [kVA] (575 V)
154
Normal overload torque (110 %) / Output S VLT,N [kVA] (690 V)
185
Normal overload torque (110 %) / Typical shaft output [kW] (550 V)
110
Normal overload torque (110 %) / Typical shaft output [HP] (575 V)
150
Normal overload torque (110 %) / Typical shaft output [kW] (690 V)
132
High overload torque (160 %) / Output current I VLT,N [A] (525-550 V)
137
High overload torque (160 %) / Output current I VLT,N [A] (551-690 V)
131
High overload torque (160 %) / Output current I VLT,MAX (60 s) [A]
197
High overload torque (160 %) / Output S VLT,N [kVA] (550 V)
131
High overload torque (160 %) / Output S VLT,N [kVA] (575 V)
130
High overload torque (160 %) / Output S VLT,N [kVA] (690 V)
157
High overload torque (160 %) / Typical shaft output [kW] (550 V)
90
High overload torque (160 %) / Typical shaft output [HP] (575 V)
125
High overload torque (160 %) / Typical shaft output [kW] (690 V)
110
Normal overload torque (110 %) / Rated input current I L,N [A] (550 V)
158
Normal overload torque (110 %) / Rated input current I L,N [A] (690 V)
155
High overload torque (160 %) / Rated input current I L,N [A] (550 V)
130
High overload torque (160 %) / Rated input current I L,N [A] (690 V)
128
Power loss, normal overload [W]
3114
Power loss, high overload [W]
2664
Show all 33 specifications
Weight IP 00 [kg]
82
Weight IP 21/Nema1 [kg]
96
Weight IP 54/Nema12 [kg]
96

Technical documents (1)

Key features

  • 110 kW at normal overload
  • Output current 162 A at normal overload
  • Mains supply 3 x 525-690 V
  • Separate ratings for normal (110 %) and high (160 %) overload
  • Discontinued by Danfoss; successor iC7-Automation

About the Danfoss VLT 5122 525-690 V

The Danfoss VLT 5122 is a 110 kW frequency converter from the VLT 5000 series for 3 x 525-690 V supplies. Danfoss's VLT 5000 design guide gives it an output current of 162 A at normal overload (110 %), with separate ratings for high overload (160 %); the full electrical data from the design guide is listed below. Danfoss's product page states that the VLT 5000 has reached the Inactive phase of its lifecycle, meaning it is discontinued and no longer in production, and names iC7-Automation as its successor.

What is the VLT 5122 525-690 V used for?

It controls the speed of a three-phase AC motor on pumps, fans, compressors, conveyors and process machinery. A failed unit stops the motor it drives.

Lifecycle and successor

Discontinued.

OEM successor: iC7-Automation

Before you order

What to photograph or confirm so the right unit is quoted.

Read the full type code on the drive's label (it starts VLT5122, followed by the voltage, enclosure, brake, filter and option codes) and send it complete: the options differ between otherwise identical 5122 units.

Alternatives for VLT 5122 525-690 V

The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.

ProductManufacturerTypeLifecycleRelationshipQty AvailablePriceAction
iC7-AutomationNamed by the manufacturer as the successorDanfossAC driveNot checked; ask usOEM successor (upgrade path)On RequestOn requestView ›
Danfoss VLT 5001 200-240 VVLT 5000 type 5001, 0.75 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5002 200-240 VVLT 5000 type 5002, 1.1 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5003 200-240 VVLT 5000 type 5003, 1.5 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5004 200-240 VVLT 5000 type 5004, 2.2 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5005 200-240 VVLT 5000 type 5005, 3.0 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5006 200-240 VVLT 5000 type 5006, 3.7 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5008 200-240 VVLT 5000 type 5008, 7.5 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5011 200-240 VVLT 5000 type 5011, 11 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5016 200-240 VVLT 5000 type 5016, 15 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5022 200-240 VVLT 5000 type 5022, 18.5 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5027 200-240 VVLT 5000 type 5027, 22 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›
Danfoss VLT 5032 200-240 VVLT 5000 type 5032, 30 kW, 3 x 200-240 VDanfossAC driveDiscontinuedSame familyOn RequestOn requestView ›

You may also be interested in

TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.

Need Danfoss VLT 5122 525-690 V? Send us the details.