Read from the product label
- Maker
- Mitsubishi Electric
- Part no.
- Q64TDV-GH
- Serial / rev.
- as printed on your unit
Image is for illustrative purposes only. Please refer to product description.
Delivery options
Mitsubishi Electric Q64TDV-GH is a MELSEC-Q analogue input module with 4 analogue input channels and 20 ms/1 channel sampling.
- Manufacturer
- Mitsubishi Electric
- Manufacturer part no.
- Q64TDV-GH
- Product family
- Mitsubishi MELSEC-Q I/O Modules
- Type
- Analog input module
- Category
- I/O modules › Analogue input and output modules
- Lifecycle
- Phased out
- OEM successor
- R60TRD4-G
- Technical datasheet
- Data sheet
Technical specifications
- Manufacturer
- Mitsubishi Electric
- Manufacturer part no.
- Q64TDV-GH
- Type
- Analog input module
- Application
- I/O module
- Used with
- MELSEC-Q base units
- Number of analog input points
- 4 points (4 channels + cold junction compensation channels)
- Number of channels
- 4 channels
- Digital output, Temperature measured value
- 16-bit signed binary value (-2700...18200: value to the first decimal place × 10)
- Digital output, Micro voltage conversion value
- 16-bit signed binary value (-25000...25000)
- Digital output, Scaling value
- 16-bit signed binary value
- Thermocouple compliance standards
- JIS C1602-1995
- Micro voltage input, Input range
- -100...+100 mV (input resistance 2 MΩ or more)
- Micro voltage input, Accuracy
- ±0.2 mV (at 25 ± 5 ˚C operating ambient temperature); ±0.8 mV (at 0...55 ˚C operating ambient temperature)
- Micro voltage input, Resolution
- 4 µV
- Resolution
- B: 0.7 ˚C; R, S:0.8 ˚C; K, T: 0.3 ˚C; E: 0.2 ˚C; J: 0.1 ˚C; N: 0.4 ˚C
- Accuracy, Thermocouple type, Measured temperature range
- Accuracy (℃) = (Conversion accuracy) + (Temperature characteristics); ; Conversion accuracy (at operating ambient temperature 25±5 ゚C); Temperature characteristic (per operating ambient temperature variation of 1 ゚C); Maximum temperature error at ambient temperature 55゚C; Effect per wiring resistance 1Ω
- Accuracy, B, 0...600 ゚C
- ―
- Accuracy, B, 600...800 ゚C
- Conversion accuracy: ±4.0 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±14.0 ˚C; Effect per wiring resistance: 0.011 ˚C/Ω
- Accuracy, B, 800...1700 ゚C
- Conversion accuracy: ±3.5 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±13.5 ˚C; Effect per wiring resistance: 0.010 ˚C/Ω
- Accuracy, B, 1700...1820 ゚C
- ―
- Accuracy, R, -50...0 ゚C
- ―
- Accuracy, R, 0...300 ゚C
- Conversion accuracy: ±4.0 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±14.0 ˚C; Effect per wiring resistance: 0.013 ˚C/Ω
- Accuracy, R, 300...1600 ゚C
- Conversion accuracy: ±3.5 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±13.5 ˚C; Effect per wiring resistance: 0.008 ˚C/Ω
- Accuracy, R, 1600...1760 ゚C
- ―
- Accuracy, S, -50...0 ゚C
- ―
- Accuracy, S, 0...300 ゚C
- Conversion accuracy: ±4.0 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±14.0 ˚C; Effect per wiring resistance: 0.013 ˚C/Ω
- Accuracy, S, 300...1600 ゚C
- Conversion accuracy: ±3.5 ˚C; Temperature characteristics: ±0.4 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±13.5 ˚C; Effect per wiring resistance: 0.008 ˚C/Ω
- Accuracy, S, 1600...1760 ゚C
- ―
- Accuracy, K, -270...-200 ゚C
- ―
- Accuracy, K, -200...0 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±8.25 ˚C; Effect per wiring resistance: 0.005 ˚C/Ω
Show all 66 specificationsShow fewer
- Accuracy, K, 0...200 ゚C
- Conversion accuracy: ±1.5 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±7.75 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, K, 200...1200 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±8.25 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, K, 1200...1370 ゚C
- ―
- Accuracy, E, -270...-200 ゚C
- ―
- Accuracy, E, -200...200 ゚C
- Conversion accuracy: ±1.5 ˚C; Temperature characteristics: ±0.15 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±5.25 ˚C; Effect per wiring resistance: 0.003 ˚C/Ω
- Accuracy, E, 200...900 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.15 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±5.75 ˚C; Effect per wiring resistance: 0.001 ˚C/Ω
- Accuracy, E, 900...1000 ゚C
- ―
- Accuracy, J, -210...-40 ゚C
- ―
- Accuracy, J, -40...200 ゚C
- Conversion accuracy: ±1.5 ˚C; Temperature characteristics: ±0.15 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±5.25 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, J, 200...750 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.15 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±5.75 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, J, 750...1200 ゚C
- ―
- Accuracy, T, -270...-200 ゚C
- ―
- Accuracy, T, -200...0 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.1 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±4.5 ˚C; Effect per wiring resistance: 0.004 ˚C/Ω
- Accuracy, T, 0...350 ゚C
- Conversion accuracy: ±1.5 ˚C; Temperature characteristics: ±0.1 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±4.0 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, T, 350...400 ゚C
- ―
- Accuracy, N, -270...-200 ゚C
- ―
- Accuracy, N, -200...0 ゚C
- Conversion accuracy: ±2.5 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±8.75 ˚C; Effect per wiring resistance: 0.007 ˚C/Ω
- Accuracy, N, 0...200 ゚C
- Conversion accuracy: ±2.0 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±8.25 ˚C; Effect per wiring resistance: 0.003 ˚C/Ω
- Accuracy, N, 200...1250 ゚C
- Conversion accuracy: ±2.5 ˚C; Temperature characteristics: ±0.25 ˚C; Maximum temperature error at ambient temperature 55 ゚C: ±8.75 ˚C; Effect per wiring resistance: 0.002 ˚C/Ω
- Accuracy, N, 1250...1300 ゚C
- ―
- Accuracy, Cold junction compensation accuracy
- ±1.0 ˚C
- Sampling cycle
- 20 ms/1 channel
- Conversion speed
- Sampling period × 3
- Absolute maximum input
- ±5 V
- Disconnection detection
- Available (each channel independent)
- Isolation method
- Between thermocouple input/micro voltage input and programmable controller power supply: Transformer; Between thermocouple input/micro voltage input channels: Transformer; Between cold junction temperature compensation channel (Pt100) and programmable controller power supply: Non-isolation
- Dielectric withstand voltage
- Between thermocouple input/micro voltage input and programmable controller power supply, between thermocouple input/micro voltage input channels: 1780 V AC rms/3 cycles (altitude 2000 m)
- Insulation resistance
- Between thermocouple input/micro voltage input and programmable controller power supply: 500 V DC, 100 MΩ or higher; Between thermocouple input/micro voltage input channels: 500 V DC, 10 MΩ or higher
- External interface,
- 18-point terminal block (M3 screw)
- Number of occupied I/O points
- 16 points (I/O assignment: Intelligent 16 points)
- Internal current consumption (5 V DC)
- 0.50 A
- External dimensions, Height
- 98 mm
- External dimensions, Width
- 27.4 mm
- External dimensions, Depth
- 112 mm
- Weight
- 0.25 kg
- General specifications
- Refer to the general specifications of the CPU module.
Technical documents (1)
Key features
- Number of analog input points: 4 points (4 channels + cold junction compensation channels)
- Number of channels: 4 channels
- Digital output, Micro voltage conversion value: 16-bit signed binary value (-25000...25000)
- Digital output, Scaling value: 16-bit signed binary value
- Thermocouple compliance standards: JIS C1602-1995
About the Mitsubishi Electric Q64TDV-GH
The Mitsubishi Electric Q64TDV-GH is a MELSEC-Q analogue input module. Mitsubishi Electric's overview: 4 channels, thermocouple (B, R, S, K, E, J, T, N), micro voltage (-100...100 mV), conversion speed: (sampling cycle x 3)/channel, 18-point terminal block, channel isolated. Mitsubishi Electric names the R60TRD4-G as its replacement model.
What is the Q64TDV-GH used for?
The Q64TDV-GH mounts on a MELSEC-Q base unit and connects field signals to the CPU, which reads or writes them each cycle.
Lifecycle and successor
Phased out.
OEM successor: R60TRD4-G
Before you order
What to photograph or confirm so the right unit is quoted.
Check the model name Q64TDV-GH on the rating plate, with the serial number and function version. Send us a photo of the rating plate and we will confirm the details before quoting.
Alternatives for Q64TDV-GH
The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.
| Product | Manufacturer | Type | Lifecycle | Relationship | Qty Available | Price | Action |
|---|---|---|---|---|---|---|---|
| R60TRD4-GNamed by the manufacturer as the successor | Mitsubishi Electric | Analog input module | Active | OEM successor (upgrade path) | On Request | On request | View › |
| Mitsubishi Electric Q64AD2DAMELSEC-Q Analogue I/O module, Analog input: 4 channels | Mitsubishi Electric | Analog I/O module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TDMELSEC-Q Analogue input module, 4 channels, thermocouple (B, R, S, K, E, J, T, N) | Mitsubishi Electric | Analog input module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64RDMELSEC-Q Analogue input module, 4 analogue input channels | Mitsubishi Electric | Analog input module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64RD-GMELSEC-Q Analogue input module, 4 analogue input channels | Mitsubishi Electric | Analog input module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCTTNMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCTTMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Discontinued | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCTTBWNMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCTTBWMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Discontinued | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCRTNMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCRTMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Discontinued | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCRTBWNMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Phased out | Same family | On Request | On request | View › |
| Mitsubishi Electric Q64TCRTBWMELSEC-Q Temperature control module, 4 temperature input channels | Mitsubishi Electric | Temperature control module | Discontinued | Same family | On Request | On request | View › |
You may also be interested in

Mitsubishi Electric
Mitsubishi Electric RY10R2
View ›
Mitsubishi Electric
Mitsubishi Electric RY10R2-TS
View ›Mitsubishi Electric
Mitsubishi Electric RY18R2A
View ›
Mitsubishi Electric
Mitsubishi Electric RY20S6
View ›
Mitsubishi Electric
Mitsubishi Electric RY40NT5P
View ›
Mitsubishi Electric
Mitsubishi Electric RY40NT5P-TS
View ›
Mitsubishi Electric
Mitsubishi Electric RY41NT2P
View ›
Mitsubishi Electric
Mitsubishi Electric RY41NT2P-TS
View ›
Mitsubishi Electric
Mitsubishi Electric RY42NT2P
View ›
Mitsubishi Electric
Mitsubishi Electric RY41NT2H
View ›
Mitsubishi Electric
Mitsubishi Electric RY40PT5P
View ›Mitsubishi Electric
Mitsubishi Electric RY40PT5P-TS
View ›
TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.