Skip to content
Industrial

6ES7531-7KF00-0AB0

Siemens AI 8xU/I/RTD/TC ST analog input module, 16 bit

Siemens
Generic illustration of a Siemens SIMATIC S7-1500 station, not a photograph of 6ES7531-7KF00-0AB0; the exact product may look different.

Image is for illustrative purposes only. Please refer to product description.

Delivery options

  • FedEx
  • DHL
  • UPS

Siemens SIMATIC S7-1500 analog input module AI 8xU/I/RTD/TC ST: 8 channels, 16-bit, accuracy 0.3 %, 4 channels for RTD, diagnostics and hardware interrupts.

Manufacturer
Siemens
Manufacturer part no.
6ES7531-7KF00-0AB0
Product family
SIMATIC S7-1500 PLC
Type
Analog input module
Lifecycle
Active product (Siemens SiePortal)
OEM successor
Not stated
Technical datasheet
Data sheet

Technical specifications

Manufacturer
Siemens
Manufacturer part no.
6ES7531-7KF00-0AB0
Type
Analog input module
Application
Analog input module
Used with
S7-1500 and ET 200MP stations
Product type designation
AI 8xU/I/RTD/TC ST
HW functional status
FS04
Firmware version
V2.0.0
Firmware version / FW update possible
Yes
Product function / I&M data
Yes; I&M0 to I&M3
Product function / Isochronous mode
No
Product function / Prioritized startup
No
Product function / Measuring range scalable
No
Product function / Scalable measured values
No
Product function / Adjustment of measuring range
No
Engineering with / STEP 7 TIA Portal configurable/integrated from version
V12 / V12
Engineering with / STEP 7 configurable/integrated from version
V5.5 SP3 / -
Engineering with / PROFIBUS from GSD version/GSD revision
V1.0 / V5.1
Engineering with / PROFINET from GSD version/GSD revision
V2.3 / -
Operating mode / Oversampling
No
Operating mode / MSI
Yes
CiR - Configuration in RUN / Reparameterization possible in RUN
Yes
CiR - Configuration in RUN / Calibration possible in RUN
Yes
Supply voltage / Rated value (DC)
24 V
Supply voltage / permissible range, lower limit (DC)
19.2 V
Supply voltage / permissible range, upper limit (DC)
28.8 V
Supply voltage / Reverse polarity protection
Yes
Input current / Current consumption, max.
255 mA; with 19.2 V supply
24 V encoder supply / Short-circuit protection
Yes
24 V encoder supply / Output current, max.
20 mA; Max. 47 mA per channel for a duration < 10 s
Show all 231 specifications
Power consumption from the backplane bus
0.7 W
Power loss, typ.
2.7 W
Address space per module / Inputs
16 byte; typical, maximum 68 bytes, see manual for details
Address space per module / Outputs
0 byte
Number of analog inputs
8
Number of analog inputs / For current measurement
8
Number of analog inputs / For voltage measurement
8
Number of analog inputs / For resistance/resistance thermometer measurement
4
Number of analog inputs / For thermocouple measurement
8
Analog inputs / permissible input voltage for voltage input (destruction limit), max.
28.8 V
Analog inputs / permissible input current for current input (destruction limit), max.
40 mA
Analog inputs / Constant measurement current for resistance-type transmitter,
150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm,
Analog inputs / typ.
Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Analog inputs / Technical unit for temperature measurement adjustable
Yes; °C/°F/K
Analog input with oversampling
No
Analog inputs / Standardization of measured values
No
Input ranges (rated values), voltages / 0 to +5 V
No
Input ranges (rated values), voltages / 0 to +10 V
No
Input ranges (rated values), voltages / 1 V to 5 V
Yes
Input ranges (rated values), voltages / 1 V to 5 V / Input resistance (1 V to 5 V)
100 kΩ
Input ranges (rated values), voltages / -1 V to +1 V
Yes
Input ranges (rated values), voltages / -1 V to +1 V / Input resistance (-1 V to +1 V)
10 MΩ
Input ranges (rated values), voltages / -10 V to +10 V
Yes
Input ranges (rated values), voltages / -10 V to +10 V / Input resistance (-10 V to +10 V)
100 kΩ
Input ranges (rated values), voltages / -2.5 V to +2.5 V
Yes
Input ranges (rated values), voltages / -2.5 V to +2.5 V / Input resistance (-2.5 V to +2.5 V)
10 MΩ
Input ranges (rated values), voltages / -25 mV to +25 mV
No
Input ranges (rated values), voltages / -250 mV to +250 mV
Yes
Input ranges (rated values), voltages / -250 mV to +250 mV / Input resistance (-250 mV to +250 mV)
10 MΩ
Input ranges (rated values), voltages / -5 V to +5 V
Yes
Input ranges (rated values), voltages / -5 V to +5 V / Input resistance (-5 V to +5 V)
100 kΩ
Input ranges (rated values), voltages / -50 mV to +50 mV
Yes
Input ranges (rated values), voltages / -50 mV to +50 mV / Input resistance (-50 mV to +50 mV)
10 MΩ
Input ranges (rated values), voltages / -500 mV to +500 mV
Yes
Input ranges (rated values), voltages / -500 mV to +500 mV / Input resistance (-500 mV to +500 mV)
10 MΩ
Input ranges (rated values), voltages / -80 mV to +80 mV
Yes
Input ranges (rated values), voltages / -80 mV to +80 mV / Input resistance (-80 mV to +80 mV)
10 MΩ
Input ranges (rated values), currents / 0 to 20 mA
Yes
Input ranges (rated values), currents / 0 to 20 mA / Input resistance (0 to 20 mA)
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), currents / -20 mA to +20 mA
Yes
Input ranges (rated values), currents / -20 mA to +20 mA / Input resistance (-20 mA to +20 mA)
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), currents / 4 mA to 20 mA
Yes
Input ranges (rated values), currents / 4 mA to 20 mA / Input resistance (4 mA to 20 mA)
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples / Type B
Yes
Input ranges (rated values), thermocouples / Type B / Input resistance (Type B)
10 MΩ
Input ranges (rated values), thermocouples / Type C
No
Input ranges (rated values), thermocouples / Type E
Yes
Input ranges (rated values), thermocouples / Type E / Input resistance (Type E)
10 MΩ
Input ranges (rated values), thermocouples / Type J
Yes
Input ranges (rated values), thermocouples / Type J / Input resistance (type J)
10 MΩ
Input ranges (rated values), thermocouples / Type K
Yes
Input ranges (rated values), thermocouples / Type K / Input resistance (Type K)
10 MΩ
Input ranges (rated values), thermocouples / Type L
No
Input ranges (rated values), thermocouples / Type N
Yes
Input ranges (rated values), thermocouples / Type N / Input resistance (Type N)
10 MΩ
Input ranges (rated values), thermocouples / Type R
Yes
Input ranges (rated values), thermocouples / Type R / Input resistance (Type R)
10 MΩ
Input ranges (rated values), thermocouples / Type S
Yes
Input ranges (rated values), thermocouples / Type S / Input resistance (Type S)
10 MΩ
Input ranges (rated values), thermocouples / Type T
Yes
Input ranges (rated values), thermocouples / Type T / Input resistance (Type T)
10 MΩ
Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOST
No
Input ranges (rated values), resistance thermometer / Cu 10
No
Input ranges (rated values), resistance thermometer / Cu 10 according to GOST
No
Input ranges (rated values), resistance thermometer / Cu 50
No
Input ranges (rated values), resistance thermometer / Cu 50 according to GOST
No
Input ranges (rated values), resistance thermometer / Cu 100
No
Input ranges (rated values), resistance thermometer / Cu 100 according to GOST
No
Input ranges (rated values), resistance thermometer / Ni 10
No
Input ranges (rated values), resistance thermometer / Ni 10 according to GOST
No
Input ranges (rated values), resistance thermometer / Ni 100
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Ni 100 / Input resistance (Ni 100)
10 MΩ
Input ranges (rated values), resistance thermometer / Ni 100 according to GOST
No
Input ranges (rated values), resistance thermometer / Ni 1000
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Ni 1000 / Input resistance (Ni 1000)
10 MΩ
Input ranges (rated values), resistance thermometer / Ni 1000 according to GOST
No
Input ranges (rated values), resistance thermometer / LG-Ni 1000
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / LG-Ni 1000 / Input resistance (LG-Ni 1000)
10 MΩ
Input ranges (rated values), resistance thermometer / Ni 120
No
Input ranges (rated values), resistance thermometer / Ni 120 according to GOST
No
Input ranges (rated values), resistance thermometer / Ni 200 according to GOST
No
Input ranges (rated values), resistance thermometer / Ni 500
No
Input ranges (rated values), resistance thermometer / Ni 500 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 10
No
Input ranges (rated values), resistance thermometer / Pt 10 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 50
No
Input ranges (rated values), resistance thermometer / Pt 50 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 100
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 100 / Input resistance (Pt 100)
10 MΩ
Input ranges (rated values), resistance thermometer / Pt 100 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 1000
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 1000 / Input resistance (Pt 1000)
10 MΩ
Input ranges (rated values), resistance thermometer / Pt 1000 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 200
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 200 / Input resistance (Pt 200)
10 MΩ
Input ranges (rated values), resistance thermometer / Pt 200 according to GOST
No
Input ranges (rated values), resistance thermometer / Pt 500
Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 500 / Input resistance (Pt 500)
10 MΩ
Input ranges (rated values), resistance thermometer / Pt 500 according to GOST
No
Input ranges (rated values), resistors / 0 to 150 ohms
Yes
Input ranges (rated values), resistors / 0 to 150 ohms / Input resistance (0 to 150 ohms)
10 MΩ
Input ranges (rated values), resistors / 0 to 300 ohms
Yes
Input ranges (rated values), resistors / 0 to 300 ohms / Input resistance (0 to 300 ohms)
10 MΩ
Input ranges (rated values), resistors / 0 to 600 ohms
Yes
Input ranges (rated values), resistors / 0 to 600 ohms / Input resistance (0 to 600 ohms)
10 MΩ
Input ranges (rated values), resistors / 0 to 3000 ohms
No
Input ranges (rated values), resistors / 0 to 6000 ohms
Yes
Input ranges (rated values), resistors / 0 to 6000 ohms / Input resistance (0 to 6000 ohms)
10 MΩ
Input ranges (rated values), resistors / PTC
Yes
Input ranges (rated values), resistors / PTC / Input resistance (PTC)
10 MΩ
Thermocouple (TC) / Temperature compensation / Parameterizable
Yes
Thermocouple (TC) / Temperature compensation / internal temperature compensation
Yes
Thermocouple (TC) / Temperature compensation / external temperature compensation via RTD
Yes
Thermocouple (TC) / Temperature compensation / Compensation for 0 °C reference point temperature
Yes; fixed value can be set
Thermocouple (TC) / Temperature compensation / Reference channel of the module
Yes
Thermocouple (TC) / Cable length / shielded, max.
800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog value generation for the inputs / Measurement principle
integrating
Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.
16 bit
Integration and conversion time/resolution per channel / Integration time, parameterizable
Yes
Integration and conversion time/resolution per channel / Integration time (ms)
2,5 / 16,67 / 20 / 100 ms
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms)
9 / 23 / 27 / 107 ms
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / additional conversion time for wire-break monitoring
9 ms (to be considered in R/RTD/TC measurement)
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / additional conversion time for resistance
150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500,
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / measurement
Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms
Integration and conversion time/resolution per channel / Interference voltage suppression for interference frequency f1 in Hz
400 / 60 / 50 / 10 Hz
Integration and conversion time/resolution per channel / Time for offset calibration (per module)
Basic conversion time of the slowest channel
Smoothing of measured values / Number of smoothing levels
4
Smoothing of measured values / parameterizable
Yes
Smoothing of measured values / Step: None
Yes
Smoothing of measured values / Step: low
Yes
Smoothing of measured values / Step: Medium
Yes
Smoothing of measured values / Step: High
Yes
Connection of signal encoders / for voltage measurement
Yes
Connection of signal encoders / for current measurement as 2-wire transducer
Yes
Connection of signal encoders / for current measurement as 2-wire transducer / Burden of 2-wire transmitter, max.
820 Ω
Connection of signal encoders / for current measurement as 4-wire transducer
Yes
Connection of signal encoders / for resistance measurement with two-wire connection
Yes; Only for PTC
Connection of signal encoders / for resistance measurement with three-wire connection
Yes; All measuring ranges except PTC; internal compensation of the cable resistances
Connection of signal encoders / for resistance measurement with four-wire connection
Yes; All measuring ranges except PTC
Errors/accuracies / Linearity error (relative to input range), (+/-)
0.02 %
Errors/accuracies / Temperature error (relative to input range), (+/-)
0.005 %/K; With TC type T 0.02 ± % / K
Errors/accuracies / Crosstalk between the inputs, max.
-80 dB
Errors/accuracies / Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)
0.02 %
Errors/accuracies / Temperature error of internal compensation
±6 °C
Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)
0.3 %
Operational error limit in overall temperature range / Current, relative to input range, (+/-)
0.3 %
Operational error limit in overall temperature range / Resistance, relative to input range, (+/-)
0.3 %
Operational error limit in overall temperature range / Resistance thermometer, relative to input range, (+/-)
Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
Operational error limit in overall temperature range / Thermocouple, relative to input range, (+/-)
Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)
0.1 %
Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)
0.1 %
Basic error limit (operational limit at 25 °C) / Resistance, relative to input range, (+/-)
0.1 %
Basic error limit (operational limit at 25 °C) / Resistance thermometer, relative to input range, (+/-)
Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
Basic error limit (operational limit at 25 °C) / Thermocouple, relative to input range, (+/-)
Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Series mode interference (peak value of interference < rated value of input range), min.
40 dB
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Common mode voltage, max.
10 V
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Common mode interference, min.
60 dB
Interrupts/diagnostics/status information / Diagnostics function
Yes
Alarms / Diagnostic alarm
Yes
Alarms / Limit value alarm
Yes; two upper and two lower limit values in each case
Diagnoses / Monitoring the supply voltage
Yes
Diagnoses / Wire break
Yes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD
Diagnoses / Short-circuit
No
Diagnoses / Group error
No
Diagnoses / Overflow/Underflow
Yes
Diagnostics indication LED / RUN LED
Yes; green LED
Diagnostics indication LED / ERROR LED
Yes; red LED
Diagnostics indication LED / MAINT LED
No
Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED)
Yes; green LED
Diagnostics indication LED / Channel status display
Yes; green LED
Diagnostics indication LED / for channel diagnostics
Yes; red LED
Diagnostics indication LED / for module diagnostics
Yes; red LED
Potential separation channels / between the channels
No
Potential separation channels / between the channels, in groups of
8
Potential separation channels / between the channels and backplane bus
Yes
Potential separation channels / between the channels and the power supply of the electronics
Yes
Permissible potential difference / between the inputs (UCM)
20 V DC
Permissible potential difference / Between the inputs and MANA (UCM)
10 V DC
Isolation tested with
707 V DC (type test)
Standards, approvals, certificates / Siemens Eco Profile (SEP)
Siemens EcoTech
Standards, approvals, certificates / Suitable for applications according to AMS 2750
Yes; Declaration of Conformity, see online support entry 109757262
Standards, approvals, certificates / Suitable for applications according to CQI-9
Yes; Based on AMS 2750 E
Ecological footprint / environmental product declaration
Yes
Ecological footprint / Global warming potential / global warming potential, (total) [CO2 eq]
38.6 kg
Ecological footprint / Global warming potential / global warming potential, (during production) [CO2 eq]
14.4 kg
Ecological footprint / Global warming potential / global warming potential, (during operation) [CO2 eq]
24.6 kg
Ecological footprint / Global warming potential / global warming potential, (after end of life cycle) [CO2 eq]
-0.44 kg
Security / signed firmware update
No
Security / securely removing data
No
Security / data integrity
No
Ambient temperature during operation / horizontal installation, min.
-25 °C; From FS08
Ambient temperature during operation / horizontal installation, max.
60 °C
Ambient temperature during operation / vertical installation, min.
-25 °C; From FS08
Ambient temperature during operation / vertical installation, max.
40 °C
Altitude during operation relating to sea level / Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity / dew point, min.
-60 °C; suitable for dry room applications
Width
35 mm
Height
147 mm
Depth
129 mm
Weight, approx.
310 g
Other / Note:
please order front connectors (screw-in/push-in) separately

Technical documents (1)

Key features

  • 8 analog inputs: voltage, current and thermocouple on all 8, RTD on 4
  • 16-bit resolution, accuracy 0.3 %
  • Integration time 2.5, 16.67, 20 or 100 ms
  • Diagnostics and hardware interrupts
  • Takes a 40-pole front connector (35 mm module)

About the Siemens 6ES7531-7KF00-0AB0

The Siemens 6ES7531-7KF00-0AB0 is the S7-1500 AI 8xU/I/RTD/TC ST analog input module. Siemens describes it with 16-bit resolution and 0.3 % accuracy; its data sheet gives voltage, current and thermocouple measurement on all eight channels and resistance thermometers on four, integration times of 2.5, 16.67, 20 or 100 ms, diagnostics and hardware interrupts. It ships with its infeed element and shield bracket. SiePortal lists it as an active product.

What is the 6ES7531-7KF00-0AB0 used for?

It brings process values into an S7-1500 or ET 200MP station: transmitter signals, thermocouples and RTDs.

Lifecycle and successor

Active product (Siemens SiePortal).

Before you order

What to photograph or confirm so the right unit is quoted.

Check the order number on the module and note the range on each channel. The front connector with the field wiring normally moves across to the replacement.

Alternatives for 6ES7531-7KF00-0AB0

The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.

ProductManufacturerTypeLifecycleRelationshipQty AvailablePriceAction
Siemens 6ES7515-2AN03-0AB0CPU 1515-2 PN, 1 MB program / 4.5 MB dataSiemensPLC CPUActive product (Siemens SiePortal)Same familyOn RequestOn requestView ›
Siemens 6ES7592-1AM00-0XB0Front connector, 40-pole, screw, for 35 mm modulesSiemensFront connectorActive product (Siemens SiePortal)Same familyOn RequestOn requestView ›

You may also be interested in

TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.