Skip to content

Siemens 6ES7531-7KF00-0AB0

AI 8xU/I/RTD/TC ST analog input module, 16 bit

Request a quote
Siemens
Siemens 6ES7531-7KF00-0AB0 AI 8xU/I/RTD/TC ST analog input module, 16 bit, photo from Siemens data sheet 6ES7531-7KF00-0AB0

Image is for illustrative purposes only. Please refer to product description.

  • FedEx
  • DHL
  • UPS
Manufacturer
Siemens
Manufacturer part number
6ES7531-7KF00-0AB0
Product family
SIMATIC S7-1500 PLC
Technical datasheet
Data sheet

Specifications

AttributeValue
TypeAnalog input module
Manufacturer lifecycleActive
Product type designationAI 8xU/I/RTD/TC ST
HW functional statusFS04
Firmware versionV2.0.0
Firmware version / FW update possibleYes
Product function / I&M dataYes; I&M0 to I&M3
Product function / Isochronous modeNo
Product function / Prioritized startupNo
Product function / Measuring range scalableNo
Product function / Scalable measured valuesNo
Product function / Adjustment of measuring rangeNo
Engineering with / STEP 7 TIA Portal configurable/integrated from versionV12 / V12
Engineering with / STEP 7 configurable/integrated from versionV5.5 SP3 / -
Engineering with / PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
Show all 228 specifications
Engineering with / PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode / OversamplingNo
Operating mode / MSIYes
CiR - Configuration in RUN / Reparameterization possible in RUNYes
CiR - Configuration in RUN / Calibration possible in RUNYes
Supply voltage / Rated value (DC)24 V
Supply voltage / permissible range, lower limit (DC)19.2 V
Supply voltage / permissible range, upper limit (DC)28.8 V
Supply voltage / Reverse polarity protectionYes
Input current / Current consumption, max.255 mA; with 19.2 V supply
24 V encoder supply / Short-circuit protectionYes
24 V encoder supply / Output current, max.20 mA; Max. 47 mA per channel for a duration < 10 s
Power consumption from the backplane bus0.7 W
Power loss, typ.2.7 W
Address space per module / Inputs16 byte; typical, maximum 68 bytes, see manual for details
Address space per module / Outputs0 byte
Number of analog inputs8
Number of analog inputs / For current measurement8
Number of analog inputs / For voltage measurement8
Number of analog inputs / For resistance/resistance thermometer measurement4
Number of analog inputs / For thermocouple measurement8
Analog inputs / permissible input voltage for voltage input (destruction limit), max.28.8 V
Analog inputs / permissible input current for current input (destruction limit), max.40 mA
Analog inputs / Constant measurement current for resistance-type transmitter,150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm,
Analog inputs / typ.Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Analog inputs / Technical unit for temperature measurement adjustableYes; °C/°F/K
Analog input with oversamplingNo
Analog inputs / Standardization of measured valuesNo
Input ranges (rated values), voltages / 0 to +5 VNo
Input ranges (rated values), voltages / 0 to +10 VNo
Input ranges (rated values), voltages / 1 V to 5 VYes
Input ranges (rated values), voltages / 1 V to 5 V / Input resistance (1 V to 5 V)100 kΩ
Input ranges (rated values), voltages / -1 V to +1 VYes
Input ranges (rated values), voltages / -1 V to +1 V / Input resistance (-1 V to +1 V)10 MΩ
Input ranges (rated values), voltages / -10 V to +10 VYes
Input ranges (rated values), voltages / -10 V to +10 V / Input resistance (-10 V to +10 V)100 kΩ
Input ranges (rated values), voltages / -2.5 V to +2.5 VYes
Input ranges (rated values), voltages / -2.5 V to +2.5 V / Input resistance (-2.5 V to +2.5 V)10 MΩ
Input ranges (rated values), voltages / -25 mV to +25 mVNo
Input ranges (rated values), voltages / -250 mV to +250 mVYes
Input ranges (rated values), voltages / -250 mV to +250 mV / Input resistance (-250 mV to +250 mV)10 MΩ
Input ranges (rated values), voltages / -5 V to +5 VYes
Input ranges (rated values), voltages / -5 V to +5 V / Input resistance (-5 V to +5 V)100 kΩ
Input ranges (rated values), voltages / -50 mV to +50 mVYes
Input ranges (rated values), voltages / -50 mV to +50 mV / Input resistance (-50 mV to +50 mV)10 MΩ
Input ranges (rated values), voltages / -500 mV to +500 mVYes
Input ranges (rated values), voltages / -500 mV to +500 mV / Input resistance (-500 mV to +500 mV)10 MΩ
Input ranges (rated values), voltages / -80 mV to +80 mVYes
Input ranges (rated values), voltages / -80 mV to +80 mV / Input resistance (-80 mV to +80 mV)10 MΩ
Input ranges (rated values), currents / 0 to 20 mAYes
Input ranges (rated values), currents / 0 to 20 mA / Input resistance (0 to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), currents / -20 mA to +20 mAYes
Input ranges (rated values), currents / -20 mA to +20 mA / Input resistance (-20 mA to +20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), currents / 4 mA to 20 mAYes
Input ranges (rated values), currents / 4 mA to 20 mA / Input resistance (4 mA to 20 mA)25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples / Type BYes
Input ranges (rated values), thermocouples / Type B / Input resistance (Type B)10 MΩ
Input ranges (rated values), thermocouples / Type CNo
Input ranges (rated values), thermocouples / Type EYes
Input ranges (rated values), thermocouples / Type E / Input resistance (Type E)10 MΩ
Input ranges (rated values), thermocouples / Type JYes
Input ranges (rated values), thermocouples / Type J / Input resistance (type J)10 MΩ
Input ranges (rated values), thermocouples / Type KYes
Input ranges (rated values), thermocouples / Type K / Input resistance (Type K)10 MΩ
Input ranges (rated values), thermocouples / Type LNo
Input ranges (rated values), thermocouples / Type NYes
Input ranges (rated values), thermocouples / Type N / Input resistance (Type N)10 MΩ
Input ranges (rated values), thermocouples / Type RYes
Input ranges (rated values), thermocouples / Type R / Input resistance (Type R)10 MΩ
Input ranges (rated values), thermocouples / Type SYes
Input ranges (rated values), thermocouples / Type S / Input resistance (Type S)10 MΩ
Input ranges (rated values), thermocouples / Type TYes
Input ranges (rated values), thermocouples / Type T / Input resistance (Type T)10 MΩ
Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer / Cu 10No
Input ranges (rated values), resistance thermometer / Cu 10 according to GOSTNo
Input ranges (rated values), resistance thermometer / Cu 50No
Input ranges (rated values), resistance thermometer / Cu 50 according to GOSTNo
Input ranges (rated values), resistance thermometer / Cu 100No
Input ranges (rated values), resistance thermometer / Cu 100 according to GOSTNo
Input ranges (rated values), resistance thermometer / Ni 10No
Input ranges (rated values), resistance thermometer / Ni 10 according to GOSTNo
Input ranges (rated values), resistance thermometer / Ni 100Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Ni 100 / Input resistance (Ni 100)10 MΩ
Input ranges (rated values), resistance thermometer / Ni 100 according to GOSTNo
Input ranges (rated values), resistance thermometer / Ni 1000Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Ni 1000 / Input resistance (Ni 1000)10 MΩ
Input ranges (rated values), resistance thermometer / Ni 1000 according to GOSTNo
Input ranges (rated values), resistance thermometer / LG-Ni 1000Yes; Standard/climate
Input ranges (rated values), resistance thermometer / LG-Ni 1000 / Input resistance (LG-Ni 1000)10 MΩ
Input ranges (rated values), resistance thermometer / Ni 120No
Input ranges (rated values), resistance thermometer / Ni 120 according to GOSTNo
Input ranges (rated values), resistance thermometer / Ni 200 according to GOSTNo
Input ranges (rated values), resistance thermometer / Ni 500No
Input ranges (rated values), resistance thermometer / Ni 500 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 10No
Input ranges (rated values), resistance thermometer / Pt 10 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 50No
Input ranges (rated values), resistance thermometer / Pt 50 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 100Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 100 / Input resistance (Pt 100)10 MΩ
Input ranges (rated values), resistance thermometer / Pt 100 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 1000Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 1000 / Input resistance (Pt 1000)10 MΩ
Input ranges (rated values), resistance thermometer / Pt 1000 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 200Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 200 / Input resistance (Pt 200)10 MΩ
Input ranges (rated values), resistance thermometer / Pt 200 according to GOSTNo
Input ranges (rated values), resistance thermometer / Pt 500Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 500 / Input resistance (Pt 500)10 MΩ
Input ranges (rated values), resistance thermometer / Pt 500 according to GOSTNo
Input ranges (rated values), resistors / 0 to 150 ohmsYes
Input ranges (rated values), resistors / 0 to 150 ohms / Input resistance (0 to 150 ohms)10 MΩ
Input ranges (rated values), resistors / 0 to 300 ohmsYes
Input ranges (rated values), resistors / 0 to 300 ohms / Input resistance (0 to 300 ohms)10 MΩ
Input ranges (rated values), resistors / 0 to 600 ohmsYes
Input ranges (rated values), resistors / 0 to 600 ohms / Input resistance (0 to 600 ohms)10 MΩ
Input ranges (rated values), resistors / 0 to 3000 ohmsNo
Input ranges (rated values), resistors / 0 to 6000 ohmsYes
Input ranges (rated values), resistors / 0 to 6000 ohms / Input resistance (0 to 6000 ohms)10 MΩ
Input ranges (rated values), resistors / PTCYes
Input ranges (rated values), resistors / PTC / Input resistance (PTC)10 MΩ
Thermocouple (TC) / Temperature compensation / ParameterizableYes
Thermocouple (TC) / Temperature compensation / internal temperature compensationYes
Thermocouple (TC) / Temperature compensation / external temperature compensation via RTDYes
Thermocouple (TC) / Temperature compensation / Compensation for 0 °C reference point temperatureYes; fixed value can be set
Thermocouple (TC) / Temperature compensation / Reference channel of the moduleYes
Thermocouple (TC) / Cable length / shielded, max.800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog value generation for the inputs / Measurement principleintegrating
Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.16 bit
Integration and conversion time/resolution per channel / Integration time, parameterizableYes
Integration and conversion time/resolution per channel / Integration time (ms)2,5 / 16,67 / 20 / 100 ms
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms)9 / 23 / 27 / 107 ms
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / additional conversion time for wire-break monitoring9 ms (to be considered in R/RTD/TC measurement)
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / additional conversion time for resistance150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500,
Integration and conversion time/resolution per channel / Basic conversion time, including integration time (ms) / measurementPt1000, Ni1000, LG-Ni1000, PTC: 4 ms
Integration and conversion time/resolution per channel / Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
Integration and conversion time/resolution per channel / Time for offset calibration (per module)Basic conversion time of the slowest channel
Smoothing of measured values / Number of smoothing levels4
Smoothing of measured values / parameterizableYes
Smoothing of measured values / Step: NoneYes
Smoothing of measured values / Step: lowYes
Smoothing of measured values / Step: MediumYes
Smoothing of measured values / Step: HighYes
Connection of signal encoders / for voltage measurementYes
Connection of signal encoders / for current measurement as 2-wire transducerYes
Connection of signal encoders / for current measurement as 2-wire transducer / Burden of 2-wire transmitter, max.820 Ω
Connection of signal encoders / for current measurement as 4-wire transducerYes
Connection of signal encoders / for resistance measurement with two-wire connectionYes; Only for PTC
Connection of signal encoders / for resistance measurement with three-wire connectionYes; All measuring ranges except PTC; internal compensation of the cable resistances
Connection of signal encoders / for resistance measurement with four-wire connectionYes; All measuring ranges except PTC
Errors/accuracies / Linearity error (relative to input range), (+/-)0.02 %
Errors/accuracies / Temperature error (relative to input range), (+/-)0.005 %/K; With TC type T 0.02 ± % / K
Errors/accuracies / Crosstalk between the inputs, max.-80 dB
Errors/accuracies / Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.02 %
Errors/accuracies / Temperature error of internal compensation±6 °C
Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)0.3 %
Operational error limit in overall temperature range / Current, relative to input range, (+/-)0.3 %
Operational error limit in overall temperature range / Resistance, relative to input range, (+/-)0.3 %
Operational error limit in overall temperature range / Resistance thermometer, relative to input range, (+/-)Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
Operational error limit in overall temperature range / Thermocouple, relative to input range, (+/-)Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)0.1 %
Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)0.1 %
Basic error limit (operational limit at 25 °C) / Resistance, relative to input range, (+/-)0.1 %
Basic error limit (operational limit at 25 °C) / Resistance thermometer, relative to input range, (+/-)Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
Basic error limit (operational limit at 25 °C) / Thermocouple, relative to input range, (+/-)Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Series mode interference (peak value of interference < rated value of input range), min.40 dB
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Common mode voltage, max.10 V
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency / Common mode interference, min.60 dB
Interrupts/diagnostics/status information / Diagnostics functionYes
Alarms / Diagnostic alarmYes
Alarms / Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses / Monitoring the supply voltageYes
Diagnoses / Wire breakYes; Only for 1 to 5 V, 4 to 20 mA, TC, R, and RTD
Diagnoses / Short-circuitNo
Diagnoses / Group errorNo
Diagnoses / Overflow/UnderflowYes
Diagnostics indication LED / RUN LEDYes; green LED
Diagnostics indication LED / ERROR LEDYes; red LED
Diagnostics indication LED / MAINT LEDNo
Diagnostics indication LED / Monitoring of the supply voltage (PWR-LED)Yes; green LED
Diagnostics indication LED / Channel status displayYes; green LED
Diagnostics indication LED / for channel diagnosticsYes; red LED
Diagnostics indication LED / for module diagnosticsYes; red LED
Potential separation channels / between the channelsNo
Potential separation channels / between the channels, in groups of8
Potential separation channels / between the channels and backplane busYes
Potential separation channels / between the channels and the power supply of the electronicsYes
Permissible potential difference / between the inputs (UCM)20 V DC
Permissible potential difference / Between the inputs and MANA (UCM)10 V DC
Isolation tested with707 V DC (type test)
Standards, approvals, certificates / Siemens Eco Profile (SEP)Siemens EcoTech
Standards, approvals, certificates / Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
Standards, approvals, certificates / Suitable for applications according to CQI-9Yes; Based on AMS 2750 E
Ecological footprint / environmental product declarationYes
Ecological footprint / Global warming potential / global warming potential, (total) [CO2 eq]38.6 kg
Ecological footprint / Global warming potential / global warming potential, (during production) [CO2 eq]14.4 kg
Ecological footprint / Global warming potential / global warming potential, (during operation) [CO2 eq]24.6 kg
Ecological footprint / Global warming potential / global warming potential, (after end of life cycle) [CO2 eq]-0.44 kg
Security / signed firmware updateNo
Security / securely removing dataNo
Security / data integrityNo
Ambient temperature during operation / horizontal installation, min.-25 °C; From FS08
Ambient temperature during operation / horizontal installation, max.60 °C
Ambient temperature during operation / vertical installation, min.-25 °C; From FS08
Ambient temperature during operation / vertical installation, max.40 °C
Altitude during operation relating to sea level / Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity / dew point, min.-60 °C; suitable for dry room applications
Width35 mm
Height147 mm
Depth129 mm
Weight, approx.310 g
Other / Note:please order front connectors (screw-in/push-in) separately

Associated Products

ImageProductDescriptionStockViewAdd to RFQ
Siemens 6ES7515-2AN03-0AB0
6ES7515-2AN03-0AB0SiemensCPU 1515-2 PN, 1 MB program / 4.5 MB dataIn stockView
Siemens 6ES7592-1AM00-0XB0
6ES7592-1AM00-0XB0SiemensFront connector, 40-pole, screw, for 35 mm modulesIn stockView

Product Questions

Is the 6ES7531-7KF00-0AB0 discontinued?

No. Its manufacturer lifecycle status is Active.

Can another Siemens SIMATIC S7-1500 part replace it?

Potential replacements must be checked against the required ratings, dimensions and connections. Sharing a family name does not establish interchangeability.

Do you ship worldwide?

Yes. TimControls ships worldwide. Parts usually ship within 3 to 7 working days of order confirmation, and the exact lead time and shipping options are stated on your quote. Include your delivery country and postal code when you ask for a quote.

TimControls is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.

Need a part? Send us the part number.

Added to cart