Image is for illustrative purposes only. Please refer to product description.
Delivery options
Siemens SIMATIC S7-300 SM 331 analog input module: 8 isolated inputs, 13-bit resolution, voltage, current, resistance, Pt100, Ni100, Ni1000, LG-Ni1000, PTC/KTY, 66 ms conversion time, 40-pole front connector.
- Manufacturer
- Siemens
- Manufacturer part no.
- 6ES7331-1KF02-0AB0
- Product family
- SIMATIC S7-300 PLC Modules
- Type
- Analog module
- Lifecycle
- Discontinued: product cancellation (Siemens SiePortal), spare part only
- OEM successor
- Not stated
- Technical datasheet
- Data sheet
Technical specifications
- Manufacturer
- Siemens
- Manufacturer part no.
- 6ES7331-1KF02-0AB0
- Type
- Analog module
- Application
- Analog I/O module
- Used with
- SIMATIC S7-300 rack (S7-300 backplane bus)
- Product function / Isochronous mode
- No
- Input current / from backplane bus 5 V DC, max.
- 90 mA
- Power loss, typ.
- 0.4 W
- Number of analog inputs
- 8
- Number of analog inputs / For resistance measurement
- 8
- Analog inputs / permissible input voltage for voltage input (destruction limit), max.
- 30 V; 12 V continuous, 30 V for max. 1 s
- Analog inputs / permissible input current for current input (destruction limit), max.
- 40 mA
- Input ranges / Voltage
- Yes
- Input ranges / Current
- Yes
- Input ranges / Thermocouple
- No
- Input ranges / Resistance thermometer
- Yes
- Input ranges / Resistance
- Yes
- Input ranges (rated values), voltages / 0 to +10 V
- Yes
- Input ranges (rated values), voltages / 0 to +10 V / Input resistance (0 to 10 V)
- 100 kΩ
- Input ranges (rated values), voltages / 1 V to 5 V
- Yes
- Input ranges (rated values), voltages / 1 V to 5 V / Input resistance (1 V to 5 V)
- 100 kΩ
- Input ranges (rated values), voltages / 1 V to 10 V
- No
- Input ranges (rated values), voltages / -1 V to +1 V
- Yes
- Input ranges (rated values), voltages / -1 V to +1 V / Input resistance (-1 V to +1 V)
- 100 kΩ
- Input ranges (rated values), voltages / -10 V to +10 V
- Yes
- Input ranges (rated values), voltages / -10 V to +10 V / Input resistance (-10 V to +10 V)
- 100 kΩ
- Input ranges (rated values), voltages / -2.5 V to +2.5 V
- No
- Input ranges (rated values), voltages / -250 mV to +250 mV
- No
- Input ranges (rated values), voltages / -5 V to +5 V
- Yes
- Input ranges (rated values), voltages / -5 V to +5 V / Input resistance (-5 V to +5 V)
- 100 kΩ
Show all 114 specificationsShow fewer
- Input ranges (rated values), voltages / -50 mV to +50 mV
- Yes
- Input ranges (rated values), voltages / -50 mV to +50 mV / Input resistance (-50 mV to +50 mV)
- 100 kΩ
- Input ranges (rated values), voltages / -500 mV to +500 mV
- Yes
- Input ranges (rated values), voltages / -500 mV to +500 mV / Input resistance (-500 mV to +500 mV)
- 100 kΩ
- Input ranges (rated values), voltages / -80 mV to +80 mV
- No
- Input ranges (rated values), currents / 0 to 20 mA
- Yes
- Input ranges (rated values), currents / 0 to 20 mA / Input resistance (0 to 20 mA)
- 100 Ω
- Input ranges (rated values), currents / -10 mA to +10 mA
- No
- Input ranges (rated values), currents / -20 mA to +20 mA
- Yes
- Input ranges (rated values), currents / -20 mA to +20 mA / Input resistance (-20 mA to +20 mA)
- 100 Ω
- Input ranges (rated values), currents / -3.2 mA to +3.2 mA
- No
- Input ranges (rated values), currents / 4 mA to 20 mA
- Yes
- Input ranges (rated values), currents / 4 mA to 20 mA / Input resistance (4 mA to 20 mA)
- 100 Ω
- Input ranges (rated values), thermocouples / Type B
- No
- Input ranges (rated values), thermocouples / Type C
- No
- Input ranges (rated values), thermocouples / Type E
- No
- Input ranges (rated values), thermocouples / Type J
- No
- Input ranges (rated values), thermocouples / Type K
- No
- Input ranges (rated values), thermocouples / Type L
- No
- Input ranges (rated values), thermocouples / Type N
- No
- Input ranges (rated values), thermocouples / Type R
- No
- Input ranges (rated values), thermocouples / Type S
- No
- Input ranges (rated values), thermocouples / Type T
- No
- Input ranges (rated values), thermocouples / Type U
- No
- Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOST
- No
- Input ranges (rated values), resistance thermometer / Cu 10
- No
- Input ranges (rated values), resistance thermometer / Ni 100
- Yes; Standard/climate
- Input ranges (rated values), resistance thermometer / Ni 100 / Input resistance (Ni 100)
- 100 MΩ
- Input ranges (rated values), resistance thermometer / Ni 1000
- Yes
- Input ranges (rated values), resistance thermometer / Ni 1000 / Input resistance (Ni 1000)
- 100 MΩ
- Input ranges (rated values), resistance thermometer / LG-Ni 1000
- Yes; Standard/climate
- Input ranges (rated values), resistance thermometer / LG-Ni 1000 / Input resistance (LG-Ni 1000)
- 100 MΩ
- Input ranges (rated values), resistance thermometer / Ni 120
- No
- Input ranges (rated values), resistance thermometer / Ni 200
- No
- Input ranges (rated values), resistance thermometer / Ni 500
- No
- Input ranges (rated values), resistance thermometer / Pt 100
- Yes; Standard/climate
- Input ranges (rated values), resistance thermometer / Pt 100 / Input resistance (Pt 100)
- 100 MΩ
- Input ranges (rated values), resistance thermometer / Pt 1000
- No
- Input ranges (rated values), resistance thermometer / Pt 200
- No
- Input ranges (rated values), resistance thermometer / Pt 500
- No
- Input ranges (rated values), resistors / 0 to 150 ohms
- No
- Input ranges (rated values), resistors / 0 to 300 ohms
- No
- Input ranges (rated values), resistors / 0 to 600 ohms
- Yes
- Input ranges (rated values), resistors / 0 to 600 ohms / Input resistance (0 to 600 ohms)
- 100 MΩ
- Input ranges (rated values), resistors / 0 to 6000 ohms
- Yes
- Input ranges (rated values), resistors / 0 to 6000 ohms / Input resistance (0 to 6000 ohms)
- 100 MΩ
- Thermocouple (TC) / Temperature compensation / Parameterizable
- No
- Thermocouple (TC) / Temperature compensation / internal temperature compensation
- No
- Thermocouple (TC) / Temperature compensation / external temperature compensation with compensations socket
- No
- Characteristic linearization / Parameterizable
- Yes
- Characteristic linearization / Parameterizable / for thermocouples
- No
- Characteristic linearization / Parameterizable / for resistance thermometer
- yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con.
- Cable length / shielded, max.
- 200 m; max. 50 m at 50 mV
- Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.
- 13 bit
- Integration and conversion time/resolution per channel / Integration time, parameterizable
- Yes; 60 / 50 ms
- Integration and conversion time/resolution per channel / Basic conversion time (ms)
- 66 / 55 ms
- Integration and conversion time/resolution per channel / Interference voltage suppression for interference frequency f1 in Hz
- 50 / 60 Hz
- Connection of signal encoders / for voltage measurement
- Yes
- Connection of signal encoders / for current measurement as 2-wire transducer
- Yes; with external supply
- Connection of signal encoders / for current measurement as 4-wire transducer
- Yes
- Connection of signal encoders / for resistance measurement with two-wire connection
- Yes
- Connection of signal encoders / for resistance measurement with three-wire connection
- Yes
- Connection of signal encoders / for resistance measurement with four-wire connection
- Yes
- Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)
- 0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V)
- Operational error limit in overall temperature range / Current, relative to input range, (+/-)
- 0.5 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
- Operational error limit in overall temperature range / Resistance, relative to input range, (+/-)
- 0.5 %; 0 to 6 kohms, 0 to 600 kohms
- Operational error limit in overall temperature range / Resistance thermometer, relative to input range, (+/-)
- 1 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG- Ni1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard)
- Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)
- 0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
- Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)
- 0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
- Basic error limit (operational limit at 25 °C) / Resistance, relative to input range, (+/-)
- 0.3 %; 0 to 6 kohms, 0 to 600 kohms
- Basic error limit (operational limit at 25 °C) / Resistance thermometer, relative to input range, (+/-)
- 1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
- Interrupts/diagnostics/status information / Diagnostics function
- No
- Alarms / Diagnostic alarm
- No
- Alarms / Limit value alarm
- No
- Diagnoses / Diagnostic information readable
- No
- Diagnostics indication LED / Group error SF (red)
- No
- Potential separation analog inputs / between the channels
- No
- Potential separation analog inputs / between the channels and backplane bus
- Yes
- Isolation tested with
- 500 V DC
- required front connector
- 40-pin
- Width
- 40 mm
- Height
- 125 mm
- Depth
- 117 mm
- Weight, approx.
- 250 g
Technical documents (1)
Key features
- 8 analog inputs, 13-bit
- Voltage, current, resistance, Pt100, Ni100, Ni1000, LG-Ni1000, PTC/KTY
- All 8 inputs usable for resistance measurement
- Isolated; 40-pin front connector
- Discontinued by Siemens on 1 October 2025; spare part only
About the Siemens 6ES7331-1KF02-0AB0
The Siemens 6ES7331-1KF02-0AB0 is an eight-channel SM 331 analog input module with 13-bit resolution. Siemens describes it for voltage, current, resistance, Pt100, Ni100, Ni1000, LG-Ni1000 and PTC/KTY inputs with a 66 ms conversion time, isolated, with a 40-pin front connector. Siemens's data sheet marks it as a spare part. Siemens names no direct successor for the order number; its route forward is migration to the S7-1500 with ET 200MP.
What is the 6ES7331-1KF02-0AB0 used for?
It reads temperatures from resistance thermometers and standard process signals in building services and process plant.
Lifecycle and successor
Discontinued: product cancellation (Siemens SiePortal), spare part only.
Before you order
What to photograph or confirm so the right unit is quoted.
Check the order number on the module and note the sensor type on each input, so the replacement is set up the same way.
Alternatives for 6ES7331-1KF02-0AB0
The manufacturer’s named successor and other parts in the same family. None is a drop-in replacement without checking wiring, I/O and configuration for your installation.
| Product | Manufacturer | Type | Lifecycle | Relationship | Qty Available | Price | Action |
|---|---|---|---|---|---|---|---|
| Siemens 6ES7315-2AH14-0AB0CPU 315-2 DP, 256 KB, MPI and PROFIBUS DP | Siemens | PLC CPU | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7315-2EH14-0AB0CPU 315-2 PN/DP, 384 KB, MPI/DP and PROFINET | Siemens | PLC CPU | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7317-2EK14-0AB0CPU 317-2 PN/DP, 1 MB, MPI/DP and PROFINET | Siemens | PLC CPU | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7314-6EH04-0AB0CPU 314C-2 PN/DP compact CPU with integrated I/O | Siemens | PLC CPU | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7313-5BG04-0AB0CPU 313C compact CPU with integrated I/O, MPI | Siemens | PLC CPU | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7321-1BL00-0AA0SM 321 digital input, 32 DI, 24 V DC | Siemens | Digital input module | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7322-1BL00-0AA0SM 322 digital output, 32 DO, 24 V DC, 0.5 A | Siemens | Digital output module | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7331-7KF02-0AB0SM 331 analog input, 8 AI, U/I/thermocouple/resistance | Siemens | Analog input module | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7332-5HF00-0AB0SM 332 analog output, 8 AO, voltage/current | Siemens | Analog output module | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6ES7307-1EA01-0AA0PS307 power supply, 120/230 V AC in, 24 V DC 5 A out | Siemens | Power supply | Phase-out announced (Siemens SiePortal) | Same family | On Request | On request | View › |
| Siemens 6GK7343-1CX10-0XE0CP 343-1 Lean communications processor, Industrial Ethernet | Siemens | Communications processor | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
| Siemens 6GK7343-1EX30-0XE0CP 343-1 communications processor, Industrial Ethernet, PROFINET IO controller | Siemens | Communications processor | Discontinued: product cancellation (Siemens SiePortal), spare part only | Same family | On Request | On request | View › |
You may also be interested in

Siemens
Siemens 6ES7972-0BA12-0XA0
View ›
Siemens
Siemens 6ES7972-0BB12-0XA0
View ›
Siemens
Siemens 6ES7972-0BA42-0XA0
View ›
Siemens
Siemens 6ES7972-0BB42-0XA0
View ›
Siemens
Siemens 6ES7972-0BA52-0XA0
View ›
Siemens
Siemens 6ES7972-0BB52-0XA0
View ›
Siemens
Siemens 6ES7972-0BA61-0XA0
View ›
Siemens
Siemens 6ES7972-0BA70-0XA0
View ›
Siemens
Siemens 6GK1500-0FC10
View ›
Siemens
Siemens 6GK1901-1BB10-2AA0
View ›
Siemens
Siemens 6GK1901-1BB11-2AA0
View ›
Siemens
Siemens 6XV1830-0EH10
View ›
TIMC is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.