Skip to content

Siemens 6ES7331-1KF02-0AB0

SM 331 analog input, 8 AI, 13 bit, U/I/resistance/Pt100/Ni

Request a quote
Siemens
Siemens 6ES7331-1KF02-0AB0 SM 331 analog input, 8 AI, 13 bit, U/I/resistance/Pt100/Ni, photo from Siemens data sheet 6ES7331-1KF02-0AB0

Image is for illustrative purposes only. Please refer to product description.

  • FedEx
  • DHL
  • UPS
Manufacturer
Siemens
Manufacturer part number
6ES7331-1KF02-0AB0
Technical datasheet
Data sheet

Specifications

AttributeValue
TypeAnalog module
Manufacturer lifecycleDiscontinued
Product function / Isochronous modeNo
Input current / from backplane bus 5 V DC, max.90 mA
Power loss, typ.0.4 W
Number of analog inputs8
Number of analog inputs / For resistance measurement8
Analog inputs / permissible input voltage for voltage input (destruction limit), max.30 V; 12 V continuous, 30 V for max. 1 s
Analog inputs / permissible input current for current input (destruction limit), max.40 mA
Input ranges / VoltageYes
Input ranges / CurrentYes
Input ranges / ThermocoupleNo
Input ranges / Resistance thermometerYes
Input ranges / ResistanceYes
Input ranges (rated values), voltages / 0 to +10 VYes
Show all 114 specifications
Input ranges (rated values), voltages / 0 to +10 V / Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), voltages / 1 V to 5 VYes
Input ranges (rated values), voltages / 1 V to 5 V / Input resistance (1 V to 5 V)100 kΩ
Input ranges (rated values), voltages / 1 V to 10 VNo
Input ranges (rated values), voltages / -1 V to +1 VYes
Input ranges (rated values), voltages / -1 V to +1 V / Input resistance (-1 V to +1 V)100 kΩ
Input ranges (rated values), voltages / -10 V to +10 VYes
Input ranges (rated values), voltages / -10 V to +10 V / Input resistance (-10 V to +10 V)100 kΩ
Input ranges (rated values), voltages / -2.5 V to +2.5 VNo
Input ranges (rated values), voltages / -250 mV to +250 mVNo
Input ranges (rated values), voltages / -5 V to +5 VYes
Input ranges (rated values), voltages / -5 V to +5 V / Input resistance (-5 V to +5 V)100 kΩ
Input ranges (rated values), voltages / -50 mV to +50 mVYes
Input ranges (rated values), voltages / -50 mV to +50 mV / Input resistance (-50 mV to +50 mV)100 kΩ
Input ranges (rated values), voltages / -500 mV to +500 mVYes
Input ranges (rated values), voltages / -500 mV to +500 mV / Input resistance (-500 mV to +500 mV)100 kΩ
Input ranges (rated values), voltages / -80 mV to +80 mVNo
Input ranges (rated values), currents / 0 to 20 mAYes
Input ranges (rated values), currents / 0 to 20 mA / Input resistance (0 to 20 mA)100 Ω
Input ranges (rated values), currents / -10 mA to +10 mANo
Input ranges (rated values), currents / -20 mA to +20 mAYes
Input ranges (rated values), currents / -20 mA to +20 mA / Input resistance (-20 mA to +20 mA)100 Ω
Input ranges (rated values), currents / -3.2 mA to +3.2 mANo
Input ranges (rated values), currents / 4 mA to 20 mAYes
Input ranges (rated values), currents / 4 mA to 20 mA / Input resistance (4 mA to 20 mA)100 Ω
Input ranges (rated values), thermocouples / Type BNo
Input ranges (rated values), thermocouples / Type CNo
Input ranges (rated values), thermocouples / Type ENo
Input ranges (rated values), thermocouples / Type JNo
Input ranges (rated values), thermocouples / Type KNo
Input ranges (rated values), thermocouples / Type LNo
Input ranges (rated values), thermocouples / Type NNo
Input ranges (rated values), thermocouples / Type RNo
Input ranges (rated values), thermocouples / Type SNo
Input ranges (rated values), thermocouples / Type TNo
Input ranges (rated values), thermocouples / Type UNo
Input ranges (rated values), thermocouples / Type TXK/TXK(L) to GOSTNo
Input ranges (rated values), resistance thermometer / Cu 10No
Input ranges (rated values), resistance thermometer / Ni 100Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Ni 100 / Input resistance (Ni 100)100 MΩ
Input ranges (rated values), resistance thermometer / Ni 1000Yes
Input ranges (rated values), resistance thermometer / Ni 1000 / Input resistance (Ni 1000)100 MΩ
Input ranges (rated values), resistance thermometer / LG-Ni 1000Yes; Standard/climate
Input ranges (rated values), resistance thermometer / LG-Ni 1000 / Input resistance (LG-Ni 1000)100 MΩ
Input ranges (rated values), resistance thermometer / Ni 120No
Input ranges (rated values), resistance thermometer / Ni 200No
Input ranges (rated values), resistance thermometer / Ni 500No
Input ranges (rated values), resistance thermometer / Pt 100Yes; Standard/climate
Input ranges (rated values), resistance thermometer / Pt 100 / Input resistance (Pt 100)100 MΩ
Input ranges (rated values), resistance thermometer / Pt 1000No
Input ranges (rated values), resistance thermometer / Pt 200No
Input ranges (rated values), resistance thermometer / Pt 500No
Input ranges (rated values), resistors / 0 to 150 ohmsNo
Input ranges (rated values), resistors / 0 to 300 ohmsNo
Input ranges (rated values), resistors / 0 to 600 ohmsYes
Input ranges (rated values), resistors / 0 to 600 ohms / Input resistance (0 to 600 ohms)100 MΩ
Input ranges (rated values), resistors / 0 to 6000 ohmsYes
Input ranges (rated values), resistors / 0 to 6000 ohms / Input resistance (0 to 6000 ohms)100 MΩ
Thermocouple (TC) / Temperature compensation / ParameterizableNo
Thermocouple (TC) / Temperature compensation / internal temperature compensationNo
Thermocouple (TC) / Temperature compensation / external temperature compensation with compensations socketNo
Characteristic linearization / ParameterizableYes
Characteristic linearization / Parameterizable / for thermocouplesNo
Characteristic linearization / Parameterizable / for resistance thermometeryes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con.
Cable length / shielded, max.200 m; max. 50 m at 50 mV
Integration and conversion time/resolution per channel / Resolution with overrange (bit including sign), max.13 bit
Integration and conversion time/resolution per channel / Integration time, parameterizableYes; 60 / 50 ms
Integration and conversion time/resolution per channel / Basic conversion time (ms)66 / 55 ms
Integration and conversion time/resolution per channel / Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Connection of signal encoders / for voltage measurementYes
Connection of signal encoders / for current measurement as 2-wire transducerYes; with external supply
Connection of signal encoders / for current measurement as 4-wire transducerYes
Connection of signal encoders / for resistance measurement with two-wire connectionYes
Connection of signal encoders / for resistance measurement with three-wire connectionYes
Connection of signal encoders / for resistance measurement with four-wire connectionYes
Operational error limit in overall temperature range / Voltage, relative to input range, (+/-)0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V)
Operational error limit in overall temperature range / Current, relative to input range, (+/-)0.5 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
Operational error limit in overall temperature range / Resistance, relative to input range, (+/-)0.5 %; 0 to 6 kohms, 0 to 600 kohms
Operational error limit in overall temperature range / Resistance thermometer, relative to input range, (+/-)1 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG- Ni1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard)
Basic error limit (operational limit at 25 °C) / Voltage, relative to input range, (+/-)0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
Basic error limit (operational limit at 25 °C) / Current, relative to input range, (+/-)0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
Basic error limit (operational limit at 25 °C) / Resistance, relative to input range, (+/-)0.3 %; 0 to 6 kohms, 0 to 600 kohms
Basic error limit (operational limit at 25 °C) / Resistance thermometer, relative to input range, (+/-)1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
Interrupts/diagnostics/status information / Diagnostics functionNo
Alarms / Diagnostic alarmNo
Alarms / Limit value alarmNo
Diagnoses / Diagnostic information readableNo
Diagnostics indication LED / Group error SF (red)No
Potential separation analog inputs / between the channelsNo
Potential separation analog inputs / between the channels and backplane busYes
Isolation tested with500 V DC
required front connector40-pin
Width40 mm
Height125 mm
Depth117 mm
Weight, approx.250 g
Phase-out announced (PM400)1 October 2023
Product cancellation (PM410)1 October 2025
Spare partYes, supplied by Siemens as a spare part only

Associated Products

ImageProductDescriptionStockViewAdd to RFQ
Siemens 6ES7331-7KF02-0AB0
6ES7331-7KF02-0AB0SiemensSM 331 analog input, 8 AI, U/I/thermocouple/resistanceIn stockView
Siemens 6ES7332-5HF00-0AB0
6ES7332-5HF00-0AB0SiemensSM 332 analog output, 8 AO, voltage/currentIn stockView
Siemens 6ES7331-7KB02-0AB0
6ES7331-7KB02-0AB0SiemensSM 331 analog input, 2 AI, U/I/thermocouple/resistanceIn stockView
Siemens 6ES7331-7NF00-0AB0
6ES7331-7NF00-0AB0SiemensSM 331 analog input, 8 AI, 16 bit, U/IIn stockView
Siemens 6ES7331-7PF01-0AB0
6ES7331-7PF01-0AB0SiemensSM 331 analog input, 8 AI, RTD, 16 bitIn stockView
Siemens 6ES7332-5HD01-0AB0
6ES7332-5HD01-0AB0SiemensSM 332 analog output, 4 AO, voltage/currentIn stockView
Siemens 6ES7334-0KE00-0AB0
6ES7334-0KE00-0AB0SiemensSM 334 analog module, 4 AI / 2 AO, 12 bitIn stockView
Siemens 6ES7331-7NF10-0AB0
6ES7331-7NF10-0AB0SiemensSM 331 analog input, 8 AI, 16 bit, U/I, 4-channel fast modeIn stockView
Siemens 6ES7331-7HF01-0AB0
6ES7331-7HF01-0AB0SiemensSM 331 analog input, 8 AI, 14 bit, 52 µs per channelIn stockView
Siemens 6ES7331-7PF11-0AB0
6ES7331-7PF11-0AB0SiemensSM 331 analog input, 8 AI, thermocouples, 16 bitIn stockView
Siemens 6ES7332-5HB01-0AB0
6ES7332-5HB01-0AB0SiemensSM 332 analog output, 2 AO, voltage/current, 12 bitIn stockView
Siemens 6ES7332-7ND02-0AB0
6ES7332-7ND02-0AB0SiemensSM 332 analog output, 4 AO, 16 bit, isolated per channelIn stockView

Product Questions

Is the 6ES7331-1KF02-0AB0 discontinued?

Yes. Its manufacturer lifecycle status is Discontinued.

Can another Siemens SIMATIC S7-300 part replace it?

Potential replacements must be checked against the required ratings, dimensions and connections. Sharing a family name does not establish interchangeability.

Do you ship worldwide?

Yes. TimControls ships worldwide. Parts usually ship within 3 to 7 working days of order confirmation, and the exact lead time and shipping options are stated on your quote. Include your delivery country and postal code when you ask for a quote.

Related Products and Accessories

TimControls is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.

Need a part? Send us the part number.

Added to cart