S7-300 End of Life: What 'Spare Parts Until 2033' Means
The S7-300 and ET 200M were cancelled in October 2025. Here is what the 2033 spare parts window covers, what it doesn't, and how to plan spares and migration.
By TimControls Technical TeamPublished Updated

Key takeaways
Every S7-300 and ET 200M order number we track, with its Siemens status, cancellation date and a link to the Siemens record.
A maintenance engineer reads 6ES7321-1FH00-0AA0 off a failed input card. Purchasing checks the family headline: cancelled in October 2025, spares until 2033. That card was cancelled a year earlier, on 1 October 2024.
In a cancelled range, the date that matters is the one on the exact order number. This list gives that date for each of the 78 order numbers we track, with the Siemens record behind it.
For what the 2033 spares window covers and how to plan spares and migration, see S7-300 End of Life: What ‘Spare Parts Until 2033’ Really Means. For the S7-400, see the S7-400 discontinued parts list.
As of October 2026, the S7-300 and ET 200M are in Siemens’ spare parts phase. Normal sales ended on 1 October 2025. Siemens still supplies most modules as spare parts, usually at higher prices and with longer lead times.
| Date | Siemens phase | What it means for this list |
|---|---|---|
| 1 October 2023 | PM400: phase-out | Normal availability ended. Most order numbers could still be ordered until cancellation. |
| 1 October 2025 | PM410: product cancellation | Most order numbers on this list moved to Discontinued on this date. |
| Until 1 October 2033 (planned) | Spare parts phase | Siemens plans to supply spares. Planned is not guaranteed, and stock is finite. |
Source: Siemens, Information about the product phase-out of S7-300 / ET 200M components (entry 109809890).
9 of the 78 order numbers do not follow the 1 October 2025 date. Siemens notes that single components can have their own dates, so a family headline is not enough to plan spares.
| Order number | Module | Siemens date | Difference |
|---|---|---|---|
| 6ES7153-1AA03-0XB0 | IM 153-1 interface module for ET 200M | Cancelled 1 October 2024 | A year before the range |
| 6ES7153-4AA01-0XB0 | IM 153-4 PN IO interface module for ET 200M, up to 12 modules | Cancelled 1 October 2024 | A year before the range |
| 6ES7321-1FF01-0AA0 | SM 321 digital input, 8 DI, 120/230 V AC | Cancelled 1 October 2024 | A year before the range |
| 6ES7321-1FH00-0AA0 | SM 321 digital input, 16 DI, 120/230V AC | Cancelled 1 October 2024 | A year before the range |
| 6ES7307-1BA01-0AA0 | PS307 power supply, 120/230 V AC in, 24 V DC 2 A out | Cancelled 1 October 2026 | A year after the range |
| 6ES7307-1EA01-0AA0 | PS307 power supply, 120/230V AC in, 24V DC, 5A out | Cancelled 1 October 2026 | A year after the range |
| 6ES7307-1KA02-0AA0 | PS307 power supply, 120/230 V AC in, 24 V DC 10 A out | Cancelled 1 October 2026 | A year after the range |
| 6ES7953-8LJ31-0AA0 | Micro Memory Card 512KB | Phase-out announced | Still on sale |
| 6ES7953-8LL31-0AA0 | Micro Memory Card 2MB | Phase-out announced | Still on sale |
Source: the SiePortal record of each order number.
Siemens names no S7-1500 successor for any order number in this list. It advises a move to the S7-1500, with ET 200MP or ET 200SP for the I/O. That means new hardware, a program converted in TIA Portal and a shutdown long enough to rewire the cabinet.
Source: Siemens, Guide for migrating S7-300/S7-400 to S7-1500 (entry 109478811).
Every status and date below is from Siemens’ record for that order number. Siemens can change a status, so the Source link in each row is the reference. Early or Late marks a date that differs from the rest of the range.
Older versions of S7-300 modules still run in many plants. This table gives the order number Siemens moved each one to within the S7-300 range. A different suffix can mean different firmware, memory or functions, so have an engineer confirm the match before you order.
| Earlier order number | Module | Siemens successor | Source |
|---|---|---|---|
| 6ES7315-2AF03-0AB0 | CPU 315-2 DP | None named | SiePortal |
| 6ES7312-1AE13-0AB0 | CPU 312 | 6ES7312-1AE14-0AB0 | SiePortal |
| 6ES7313-5BF03-0AB0 | CPU 313C | 6ES7313-5BG04-0AB0 | SiePortal |
| 6ES7314-1AF10-0AB0 | CPU 314 | 6ES7314-1AG14-0AB0 | SiePortal |
| 6ES7314-1AG13-0AB0 | CPU 314 | 6ES7314-1AG14-0AB0 | SiePortal |
| 6ES7314-6CF00-0AB0 | CPU 314C-2 DP | 6ES7314-6CH04-0AB0 | SiePortal |
| 6ES7314-6CG03-0AB0 | CPU 314C-2 DP | 6ES7314-6CH04-0AB0 | SiePortal |
| 6ES7315-2AG10-0AB0 | CPU 315-2 DP | 6ES7315-2AH14-0AB0 | SiePortal |
| 6ES7315-2EG10-0AB0 | CPU 315-2 PN/DP | 6ES7315-2EH14-0AB0 | SiePortal |
| 6ES7315-2EH13-0AB0 | CPU 315-2 PN/DP | 6ES7315-2EH14-0AB0 | SiePortal |
| 6ES7317-2AJ10-0AB0 | CPU 317-2 DP | 6ES7317-2AK14-0AB0 | SiePortal |
| 6ES7317-2EJ10-0AB0 | CPU 317-2 PN/DP | 6ES7317-2EK14-0AB0 | SiePortal |
| 6ES7317-2EK13-0AB0 | CPU 317-2 PN/DP | 6ES7317-2EK14-0AB0 | SiePortal |
| 6ES7318-3EL00-0AB0 | CPU 319-3 PN/DP | 6ES7318-3EL01-0AB0 | SiePortal |
Source: each earlier number’s own Siemens record.
A status in this list tells you what Siemens says about an order number. It does not confirm that a unit is in stock, where it is or what condition it is in.
Two modules with the same name can differ in order number suffix, product version and firmware. Send us all three and we confirm the match before we quote.
| Information | What to provide |
|---|---|
| Order number | The full number from the label, including the final block |
| Version | The product version (the 'ES' or 'FS' marking) |
| Firmware | On CPUs, the firmware version |
| Photos | The nameplate and the front of the module |
| Quantity and date | How many, and when you need them on site |
| Condition | Which conditions you accept: new sealed, new surplus, used, refurbished |
Download the list
All 78 order numbers in one spreadsheet: the Siemens status and dates, the successor Siemens names, the part page and the Siemens record for each.
Download the list (CSV)Sources. Siemens, Information about the product phase-out of S7-300 / ET 200M components (entry 109809890). Siemens, Guide for migrating S7-300/S7-400 to S7-1500 (entry 109478811). Siemens SiePortal product records for each order number. Statuses can change; the Siemens record is the reference. More on the timetable: what S7-300 end of life means.
Alternative*: the module Siemens lists for this order number in its migration guide (entry 109478811, V1.1, May 2017). Siemens says the listed hardware must not be treated as equivalent without checking the application. It is a migration, not a direct replacement: it needs new hardware and a converted program.
Updated: 6ES7307-1EA01-0AA0 (PS 307 power supply, 24 V DC 5 A). Siemens moved it from phase-out announced (PM400) to product cancellation (PM410) on 1 October 2026. A year after the rest of the S7-300 family, which Siemens cancelled on 1 October 2025. We added this change to the list on 9 October 2026, from SiePortal.
The S7-300 and ET 200M were cancelled in October 2025. Here is what the 2033 spare parts window covers, what it doesn't, and how to plan spares and migration.