Image is for illustrative purposes only. Please refer to product description.
- Manufacturer
- Siemens
- Manufacturer part number
- 6ES7153-1AA03-0XB0
- Product family
- SIMATIC ET 200M Remote I/O
- Category
- PLCs and I/O › Remote I/O heads and couplers
- Technical datasheet
- Data sheet
Specifications
| Attribute | Value |
|---|---|
| Type | Interface module |
| Manufacturer lifecycle | Discontinued |
| Product type designation | IM 153-1 DP ST |
| Vendor identification (VendorID) | 801Dh |
| Supply voltage / Rated value (DC) | 24 V |
| Supply voltage / permissible range, lower limit (DC) | 20.4 V |
| Supply voltage / permissible range, upper limit (DC) | 28.8 V |
| external protection for power supply lines (recommendation) | not necessary |
| Mains buffering / Mains/voltage failure stored energy time | 5 ms |
| Input current / Current consumption, max. | 350 mA; At 24 V DC |
| Input current / Inrush current, typ. | 2.5 A |
| Input current / I²t | 0.1 A²·s |
| Output voltage / Rated value (DC) | 5 V |
| Output current / for backplane bus (5 V DC), max. | 1 A |
| Power loss, typ. | 3 W |
Show all 49 specificationsShow fewer specifications
| Address space per module / Inputs | 128 byte |
|---|---|
| Address space per module / Outputs | 128 byte |
| Hardware configuration / number of modules per DP device interface, max. | 8 |
| Interfaces / Transmission procedure | RS 485 |
| Interfaces / Transmission rate, max. | 12 Mbit/s |
| 1. Interface / automatic detection of transmission rate | Yes |
| Interface types / Output current of the interface, max. | 90 mA |
| Interface types / Design of the connection | 9-pin sub D socket |
| PROFIBUS DP device / GSD file | (for DPV1) SIEM801D.GSD; SI01801D.GSG |
| PROFIBUS DP device / automatic baud rate search | Yes |
| Protocols / Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 |
| Protocols (Ethernet) / TCP/IP | No |
| PROFIBUS DP / Number of node addresses, max. | 1 to 125 permitted |
| PROFIBUS DP / Services / SYNC capability | Yes |
| PROFIBUS DP / Services / FREEZE capability | Yes |
| PROFIBUS DP / Services / Direct data exchange (slave-to-slave communication) | Yes; Sender |
| Potential separation exists | Yes |
| Isolation tested with | Isolation voltage 500 V |
| IP degree of protection | IP20 |
| Ambient temperature during operation / min. | 0 °C |
| Ambient temperature during operation / max. | 60 °C |
| Ambient temperature during operation / horizontal installation, min. | 0 °C |
| Ambient temperature during operation / horizontal installation, max. | 60 °C |
| Ambient temperature during operation / vertical installation, min. | 0 °C |
| Ambient temperature during operation / vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level / Installation altitude above sea level, max. | 3 000 m |
| Configuration software / STEP 7 | STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
| Width | 40 mm |
| Height | 125 mm |
| Depth | 117 mm |
| Weight, approx. | 360 g |
| Phase-out announced (PM400) | 1 October 2023 |
| Product cancellation (PM410) | 1 October 2024 |
| Spare part | Yes, supplied by Siemens as a spare part only |
Description
The Siemens 6ES7153-1AA03-0XB0 is the IM 153-1, the standard interface module of an ET 200M station. Siemens's data sheet gives up to 8 S7-300 modules per station, a PROFIBUS DP address from 1 to 125 and a 24 V DC supply, from which it feeds 5 V DC to the backplane bus. SiePortal shows its product cancellation on 1 October 2024, a year before most of the S7-300 range, and Siemens's data sheet marks it as a spare part. Siemens's route forward is the ET 200MP I/O system.
Application: PROFIBUS DP interface for ET 200M
Used with: ET 200M station on PROFIBUS DP
What is the 6ES7153-1AA03-0XB0 used for?
It sits at the left of an ET 200M rack and connects that rack's I/O modules to the PROFIBUS DP master, usually an S7-300 or S7-400 CPU. If it fails, every module in the station drops off the bus.
Key features
- Head module of an ET 200M station on PROFIBUS DP
- Up to 8 S7-300 I/O modules per station
- PROFIBUS address 1 to 125
- 24 V DC supply; 5 V DC to the backplane bus
- Discontinued by Siemens on 1 October 2024; spare part only
Documents and Resources
Associated Products
| Image | Product | Description | Stock | View | Add to RFQ |
|---|---|---|---|---|---|
![]() | 6ES7153-2BA10-0XB0Siemens | IM 153-2 High Feature interface module for ET 200M, up to 12 modules | In stock | View | |
![]() | 6ES7153-4AA01-0XB0Siemens | IM 153-4 PN IO interface module for ET 200M, up to 12 modules | In stock | View | |
![]() | 6ES7195-7HB00-0XA0Siemens | ET 200M active bus module for two 40 mm I/O modules | In stock | View | |
![]() | 6ES7195-7HC00-0XA0Siemens | ET 200M active bus module for one 80 mm I/O module | In stock | View | |
![]() | 6ES7195-7HD10-0XA0Siemens | ET 200M active bus module for two redundant IM 153-2 | In stock | View |
Product Questions
Is the 6ES7153-1AA03-0XB0 discontinued?
Yes. Its manufacturer lifecycle status is Discontinued.
Can another Siemens SIMATIC ET 200M part replace it?
Potential replacements must be checked against the required ratings, dimensions and connections. Sharing a family name does not establish interchangeability.
Do you ship worldwide?
Yes. TimControls ships worldwide. Parts usually ship within 3 to 7 working days of order confirmation, and the exact lead time and shipping options are stated on your quote. Include your delivery country and postal code when you ask for a quote.
Latest news
TimControls is an independent distributor. Manufacturer names and logos are the property of their respective owners and identify products we source; they do not imply manufacturer authorization or affiliation.